Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-01-28 15:24:41*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 ACCESS TO AND/OR EGRESS FROM THE OTHER FLOORS OF THE
 BUILDING.
  
 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED. CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF THIS
 CODE IS APPLICABLE SINCE THE SCOPE WORK IS FOR
 ALTERATIONS, MODERNIZATIONS, OR RENOVATIONS OF AN
 EXISTING BUSINESS OCCUPANCY.
  
 4. PLEASE INDICATE IF THIS FLOOR/BUILDING IS FIRE
 SPRINKLERED. IF SO, PROVIDE A FIRE SPRINKLER LAYOUT FOR
 THE FOURTH FLOOR.
  
 5. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. FIRE DOORS SHALL COMPLY WITH NFPA 80.
  
 7. CLARIFYVERIFY VERBAGE ON DRAWING A2.1 DOOR HARDWARE
 NOTE #3, UNDER THE DOOR SCHEDULE. IS THIS WORD "EXIST"
 OR "EXITS" ?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  