| Plan Review Notes For Permit 08120274 |
| Permit Number |
08120274 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-28 15:24:41 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH | | | ACCESS TO AND/OR EGRESS FROM THE OTHER FLOORS OF THE | | | BUILDING. | | | | | | 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF THIS | | | CODE IS APPLICABLE SINCE THE SCOPE WORK IS FOR | | | ALTERATIONS, MODERNIZATIONS, OR RENOVATIONS OF AN | | | EXISTING BUSINESS OCCUPANCY. | | | | | | 4. PLEASE INDICATE IF THIS FLOOR/BUILDING IS FIRE | | | SPRINKLERED. IF SO, PROVIDE A FIRE SPRINKLER LAYOUT FOR | | | THE FOURTH FLOOR. | | | | | | 5. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6. FIRE DOORS SHALL COMPLY WITH NFPA 80. | | | | | | 7. CLARIFYVERIFY VERBAGE ON DRAWING A2.1 DOOR HARDWARE | | | NOTE #3, UNDER THE DOOR SCHEDULE. IS THIS WORD "EXIST" | | | OR "EXITS" ? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|