| Date |
Text |
| 2008-12-30 09:12:38 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC |
| | 13-101.1,13-101.1.3,13-400.0.C.4 ETC |
| | THE SUBMITTED PROPOSED METHOD OF CALCULATIONS WAS FOR |
| | *WHOLE BUILDING COMPLIANCE* ON METHOD *A*FLA-COM. |
| | PLEASE EXPLAIN WHERE IN THE CODE DOES IT PERMIT METHOD |
| | *A* FOR WHOLE BUILDING COMPLIANCE TO BE USED FOR THE |
| | BUILD OUT OF A SHELL SPACE. |
| | |
| | PLANS CONTAIN SPACE BY SPACE FROM TABLE *B*. |
| | PLEASE SEE 13-415.2.ABC.1. THE CODE DOES NOT PERMIT THE |
| | USE OF MULTIPLE METHODS. |
| | IN EITHER CASE THE SUBMITTED INPUT DATA REPORT DOES NOT |
| | MATCH THE SUBMITTED PLANS. FOR EXAMPLE: PLEASE SEE ZONE |
| | #1 WHICH ONLY LIST A TOTAL OF FOUR FIXTURES. HOW IS |
| | THIS POSSIBLE WHEN THE LOBBY ON THE PLANS CLEARLY |
| | INDICATES SEVERAL MORE FIXTURES? IN THE LOBBY ALONE |
| | THERE A TOTAL OF 8 *M* FIXTURES ALONE. |
| | |
| | ** THIS IS ONE EXAMPLE: |
| | PLEASE SEE THE TOTAL AMOUNT OF DESIGN WATTAGE SHOWN ON |
| | SHEET E1.1 IS LESS THAN THE ACTUAL TOTAL WATTAGE OF |
| | FIXTURES SHOWN ON PLANS. THE TOTAL ON *A* FIXTURES IS |
| | ABOVE 8300. PLEASE BE SURE TO GO OVER ALL FIXTURES, THE |
| | WATTAGE OF EACH AND THE NUMBER OF FIXTURES. |
| | |
| | 2) NOTE: PLEASE PROVIDE INFORMATION ON THE MULTI-GANG |
| | BATHROOM OCCUPANCY SENSORS. DO THESE CONTAIN DUAL |
| | TECHNOLOGIES? |
| | NFPA-101 7.8. |
| | |
| | 3) NOTE: PLEASE SEE THE LOAD ON PANEL LA EXCEEDS THE |
| | BREAKER RATING IN PANEL *L* WHICH FEEDS THIS PANEL. THE |
| | LOAD SHOWN IS 33AMPS YET THERE IS ONLY A 25AMP BREAKER |
| | FEEDING THIS PANEL. |
| | 240,310,215 ETC |
| | FBC 106.1.1 |
| | |
| | 4) NOTE: THE WATER HEATER IS SHOWN BEING FED FROM A TWO |
| | POLE RECEPTACLE WHICH IS NOT PERMITTED. PLEASE SHOW THE |
| | REQUIRED DISCONNECT. 422.30,422.31 |
| | |
| | 5) NOTE: PLEASE SHOW ALL HORN, HORN/STROBE LOCATIONS, |
| | HEIGHTS AND LEVELS OF DEVICES TO MEET ADA COMPLIANCE. |
| | PLEASE SEE FBC 11-4.28.1,.2 AND .3. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |