Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-30 09:12:38** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE FBC
 13-101.1,13-101.1.3,13-400.0.C.4 ETC
 THE SUBMITTED PROPOSED METHOD OF CALCULATIONS WAS FOR
 *WHOLE BUILDING COMPLIANCE* ON METHOD *A*FLA-COM.
 PLEASE EXPLAIN WHERE IN THE CODE DOES IT PERMIT METHOD
 *A* FOR WHOLE BUILDING COMPLIANCE TO BE USED FOR THE
 BUILD OUT OF A SHELL SPACE.
  
 PLANS CONTAIN SPACE BY SPACE FROM TABLE *B*.
 PLEASE SEE 13-415.2.ABC.1. THE CODE DOES NOT PERMIT THE
 USE OF MULTIPLE METHODS.
 IN EITHER CASE THE SUBMITTED INPUT DATA REPORT DOES NOT
 MATCH THE SUBMITTED PLANS. FOR EXAMPLE: PLEASE SEE ZONE
 #1 WHICH ONLY LIST A TOTAL OF FOUR FIXTURES. HOW IS
 THIS POSSIBLE WHEN THE LOBBY ON THE PLANS CLEARLY
 INDICATES SEVERAL MORE FIXTURES? IN THE LOBBY ALONE
 THERE A TOTAL OF 8 *M* FIXTURES ALONE.
  
 ** THIS IS ONE EXAMPLE:
 PLEASE SEE THE TOTAL AMOUNT OF DESIGN WATTAGE SHOWN ON
 SHEET E1.1 IS LESS THAN THE ACTUAL TOTAL WATTAGE OF
 FIXTURES SHOWN ON PLANS. THE TOTAL ON *A* FIXTURES IS
 ABOVE 8300. PLEASE BE SURE TO GO OVER ALL FIXTURES, THE
 WATTAGE OF EACH AND THE NUMBER OF FIXTURES.
  
 2) NOTE: PLEASE PROVIDE INFORMATION ON THE MULTI-GANG
 BATHROOM OCCUPANCY SENSORS. DO THESE CONTAIN DUAL
 TECHNOLOGIES?
 NFPA-101 7.8.
  
 3) NOTE: PLEASE SEE THE LOAD ON PANEL LA EXCEEDS THE
 BREAKER RATING IN PANEL *L* WHICH FEEDS THIS PANEL. THE
 LOAD SHOWN IS 33AMPS YET THERE IS ONLY A 25AMP BREAKER
 FEEDING THIS PANEL.
 240,310,215 ETC
 FBC 106.1.1
  
 4) NOTE: THE WATER HEATER IS SHOWN BEING FED FROM A TWO
 POLE RECEPTACLE WHICH IS NOT PERMITTED. PLEASE SHOW THE
 REQUIRED DISCONNECT. 422.30,422.31
  
 5) NOTE: PLEASE SHOW ALL HORN, HORN/STROBE LOCATIONS,
 HEIGHTS AND LEVELS OF DEVICES TO MEET ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2 AND .3.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  