Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-24 15:45:56BUILDING PLAN REVIEW
 PERMIT: 08120274
 ADD: 303 BANYAN / 4TH FLOOR
 CONT: LCI CONSTRUCTION
 TEL: (561)578-5930
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B)INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS AND 2004 EXISTING
 BUILDING CODE WITH 2007 SUPPLEMENTS.
  
 2) ENERGY CODE , THE PROJECT SUMMARY INDICATES WHOLE
 METHOD "A" WAS SUBMITTED WHOLE BUILDING PERFORMANCE
 METHOD, THIS IS A 4TH FLOOR TENANT BUILD-OUT NOT A
 WHOLE BUILDING. PLEASE REVIEW 13-101.1.3. RENOVATIONS
 AND 13-202 DEFINITION FOR RENOVATIONS. BY DEFINTION
 THIS IS NOT A RENOVATION.SEE 13-400.0.C.4. EXISTING
 BUILDINGS NOT MEETING THE DEFINTION OFA RENOVATION IN
 WHICH NEW HEATING,COOLING,WATER HEATING, ELECTRICAL OR
 LIGHTING SYSTEMS ARE INSTALLED SHALL MEET THE BASIC
 PRESCRIPTIVE MINIMUM EFFICIENCIES LISTED IN THE CODE
 FOR THE SYSTEMS BEING CHANGED.
  
 3) SHEET A1.1:
  
 3A) DOOR# 45& 6, BOTH ARE INDICATED AS A 2'-6" DOOR ON
 THE DOOR SCHEDULE, 11-4.13.5 MINIMUM CLEAR OPENING IS
 32" , OPENINGS MORE THAN 24 INCHES IN DEPTH SHALL
 COMPLY WITH SECTIONS 11-4.2.1 AND 11-4.3.3.
 3B) DOOR# 42 REQUIRES 1'-6" CLEAR ON THE PULL SIDE,
 PLEASE REVIEW 11-4.13.6. MANEUVERING CLEARENCES AT
 DOORS.
  
 3C) ROOM # 127 THE EMPLOYEE LOUNGE INDICATES A SIDE
 APPROACH, AND SHEET A4.1 DETAIL# 4 ALSO INDICATE DOORS
 ON THE FRONT MAKING IT IMPOSSIBLE FOR A FRONT APPROACH.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
  
 4) SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS
 HUNG FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF
 ATTACHMENT METHOD WILL BE USED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 5) SHEET A3.1 DETAIL# 14 INDICATES A FIRESTOPPING AT
 THE 4TH FLOOR MEZZANINE LEVEL, ITHERE ARE NO PLANS OR
 DETAILS FOR WORK TO BE COMPLETED ON THAT LEVEL, OR PART
 OF THIS PERMIT?
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.