Plan Review Notes
Plan Review Notes For Permit 08120259
Permit Number 08120259
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-24 10:48:24** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SUBMIT A LETTER OF UNDERSTANDING
 BETWEEN BASE BUILDING CONTRACTOR AND SUB CONTRACTOR AS
 THE BASE BUILDING DOES NOT CONTAIN A CERTIFICATE OF
 OCCUPANCY.
  
 2) NOTE: MISSING LICENSING INFORMATION AND OTHER
 INFORMATION ON TITLE BLOCKS PER FAC 61G1-16.004 FOR
 ARCHITECTURAL FIRM.
  
 3) NOTE: PLEASE SEE FS 553.73 AS THE ADOPTED CODES BY
 THE STATE OF FLORIDA IS NOT SHOWN ON PLANS. THE STATE
 OF FLORIDA IS UNDER THE 2004 FBC WITH 2007 REVISIONS
 AND ALSO UNDER THE 2005 NFPA-70 (NATIONAL ELECTRICAL
 CODE).
 PLEASE LIST ON PLANS AS FOLLOWS FOR THIS REVIEWER AND
 SEE POSSIBLE COMMENTS FROM OTHER TRADES.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 4) NOTE: PLEASE SHOW NEW OR EXISTING HORN, STROBE AND
 PULL STATION LOCATIONS IN COMPLIANCE WITH NFPA-72 AND
 ALSO CHAPTER 11 OF THE FBC FOR ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2, AND .3.
  
 5) NOTE: PLEASE SHOW NEW OR EXISTING LIGHTING IN
 COMPLIANCE FOR EGRESS UNDER NORMAL AND EMERGENCY
 CONDITIONS.
 NFPA-101 7.8,7.9
  
 6) NOTE: PLEASE SHOW NEW OR EXISTING LIGHTING CONTROLS
 IN COMPLIANCE WITH FBC 13-415.1.ABC.1.1,.1.2, .1.3.
  
 7) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2
 FOR INTERIOR LIGHTING PERFORMANCE LEVELS FOR NEW BEING
 INSTALLED. AS THE PLANS DO NOT INDICATE ANY LIGHTING,
 THE LIGHTING DENSITY LEVELS CAN NOT BE DETERMINED FOR
 CODE COMPLIANCE AT THIS TIME.
  
 8) NOTE: COLOR CODING SHALL BE BROWN, PURPLE, YELLOW
 FOR 277/480V AS ON BASE BUILDING. ORANGE IS THE COLOR
 BY THE NEC WHICH IS SET ASIDE FOR DELTA HIGH LEG
 SYSTEMS. THIS IS NOT SUCH A SYSTEM.
 PLEASE REVISE TO MATCH EXISTING.
 90.4
  
  
 ** THE PLANS ARE MISSING INFORMATION NEEDED TO SHOW
 MINIMUM CODE COMPLIANCE FOR SEVERAL ITEMS AS LISTED
 ABOVE. EACH RECORD SET OF PLANS FOR PERMITTED WORK
 NEEDS TO SHOW THIS AS THEY DO NOT CONTAIN BASE BUILDING
 INFORMATION.
 ** AS SOME INFORMATION IS MISSING THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  