2009-07-07 16:46:26REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A-1 REVISION INDEX SIGNED, SEALED & DATED
 04-08-09 IN OUR FILE FOR PUBLIC RECORD SHOWS REVISION 2
 AS THE LAST REVISION. NEW SHEET A-1 SUBMITTED AS A
 REVISION STILL ONLY SHOWS REVISION 2 IN THE REVISION
 INDEX. PLEASE INDICATE WHAT THE NEW REVISION NUMBER
 WILL BE IN THE INDEX. ALSO THERE ARE CHANGES TO THE
 FLOOR PLAN THAT HAVE NO CLOUD OR REVISION NUMBER
 INDICATING THE REVISION. PLEASE CLOUD AND NUMBER ALL
 REVISIONS SUBMITTED. SECTION 106.1.3.
  
 2. THE 8X11 SHEETS SUBMITTED AS REV. E1 DO NOT REFLECT
 SHEET A-1. PLEASE CORRELATE. SECTION 106.1.1.
  
 3. SHT A-1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THE FLOOR PLAN SHOWS A SHOWER AND
 DIFFERENT LOCATIONS FOR THE FIXTURES. ALSO THE NEW
 FLOOR PLAN DOES NOT INDICATE A KITCHEN SINK. PLEASE
 CLARIFY & CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  