2009-06-23 11:01:36 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 SHEET E-1 MUST BE REVISED IN IT'S ENTIRETY.
  
 1} THE PARTIAL SHEET SUBMITTED DOES NOT REFLECT THE
 CHANGES IN THE RATING OF PANEL "B" DISCONNECT PER
 ARTICLE 408.36 NEC (100 AMP PANEL FED FROM A 125 AMP
 DISCONNECT)
  
 2} THE RISER DIAGRAM TO A 100 AMP PANEL 215.5 NEC.
  
 3} THE LOAD CALCULATIONS (REMOVING THE KITCHEN AND ?)
 220.
  
 4} ANY CONDUIT AND CONDUCTOR CHANGES.215.5
  
 SHEET A-1 DOES NOT INDICATE THE KITCHEN REMOVAL AND
 RECONFIGURATION OF SPACE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  