| Plan Review Notes For Permit 08120242 |
| Permit Number |
08120242 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-06-23 11:01:36 | | | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | SHEET E-1 MUST BE REVISED IN IT'S ENTIRETY. | | | | | | 1} THE PARTIAL SHEET SUBMITTED DOES NOT REFLECT THE | | | CHANGES IN THE RATING OF PANEL "B" DISCONNECT PER | | | ARTICLE 408.36 NEC (100 AMP PANEL FED FROM A 125 AMP | | | DISCONNECT) | | | | | | 2} THE RISER DIAGRAM TO A 100 AMP PANEL 215.5 NEC. | | | | | | 3} THE LOAD CALCULATIONS (REMOVING THE KITCHEN AND ?) | | | 220. | | | | | | 4} ANY CONDUIT AND CONDUCTOR CHANGES.215.5 | | | | | | SHEET A-1 DOES NOT INDICATE THE KITCHEN REMOVAL AND | | | RECONFIGURATION OF SPACE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|