2009-04-24 08:06:54BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE WINDOW MULLION SIZE TO MEET DESIGN PRESSURES.
 SEE PRODUCT APPROVAL.
 2- CREDIT FOR CEILING FANS ON THE ENERGY CALCULATIONS.
 NEED TO SPECIFY SPECIFIC FAN SIZE ON EACH ROOM AS
 REQUIRED BY TABLE 13-607.1.A.1 FBC 2004.
 3- ITEM #7 ON THE ENERGY CALCULATIONS REQUIRES LABEL ON
 GLASS TO VERIFY COMPLIANCE WITH SPECIFIED U-FACTOR AND
 SHGC FACTOR.
 4- BEDROOMS EGRESS WINDOWS TO HAVE 24" MIN. CLEAR
 HEIGHT AS REQUIRED BY SEC. R310.1.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 5- SPECIFY ROOF SHEATHING NAIL SPACING. NEED 8D RING
 SHANK NAILS AND NEED TO BE 4"O.C. AT ROOF ZONE 3# AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  