| 2009-03-13 15:18:01 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 EXISING BUILDING |
| | FBC-2004 RESIDENTIAL |
| | |
| | 1. OK |
| | 2. OK |
| | 2. OK |
| | |
| | ********NEW COMMENT******** |
| | |
| | 1B. ONLY THE FIXTURES WITHIN THE BATHROOM SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. SECTION 909.1. THE KITCHEN SINK IN THE GUEST |
| | HOUSE SHALL BE INDIVIDUALLY VENTED AND CONNECT |
| | DOWNSTREAM OF THE WATER CLOSET. |
| | |
| | 2B. THE ENERGENCY EFFICIENCY SUBMITTAL INDICATES A 50 |
| | GAL. WATER HEATER BUT THE FLOOR PLAN SHOWS A 24 KW |
| | INSTA-HOT WATER HEATER FOR THE MAIN HOURS AND A 14.4 KW |
| | FOR THE GUEST HOUSE. PLEASE SHOW THE LOCATION OF THE 50 |
| | GALLON WATER HEATER, AND UPDATE THE ENERGY EFFICINECY |
| | SUBMITTAL TO SHOW ALL WATER HEATERS. ALSO PER SECTION |
| | 13-101.2.3 RENOVATED BUILDINGS SHALL MEET THE |
| | PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD C OF |
| | SUBCHAPTER 13-6 FOR RESIDENTIAL APPLICATIONS OF THE |
| | CODE. METHOD A WAS SUBMITTED. - PER SECTION |
| | 12-101.2.5.1 THE GUEST HOUSE IS CONSIDERED A SEPARATE |
| | RESIDENCE AND SEPARATE ENERGY EFFICIENCY CODE SUBMITTAL |
| | IS REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |