| 2009-03-02 16:37:45 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMRNENTS FROM SHEET E-1, UNLESS NOTED OTHERWISE |
| | AND ARE GENERATED BY PLAN CHANGES FROM THE PREVIOUS |
| | REVIEW. |
| | |
| | 1} THE 100 AMP DISCONNECTS AND THE #4 |
| | CONDUCTORS(310.15(B)(6) FOR THE GUEST HOUSE DO NOT MEET |
| | THE REQUIREMENTS OF 225.39 RATING OF DISCONNECT: |
| | THE FEEDER OR BRANCH-CIRCUIT DISCONNECTING MEANS SHALL |
| | HAVE A RATING OF NOT LESS THAN THE LOAD TO BE SUPPLIED, |
| | DETERMINED IN ACCORDANCE WITH PARTS I AND II OF ARTICLE |
| | 220 FOR BRANCH CIRCUITS, PARTS III OR IV OF ARTICLE 220 |
| | FOR FEEDERS, OR PART V OF ARTICLE 220 FOR FARM LOADS. |
| | IN NO CASE SHALL THE RATING BE LOWER THAN SPECIFIED IN |
| | 225.39(A), (B), (C), OR (D).*** THE LOAD FOR PANEL "B" |
| | IS CALCULATED AT 103 AMPS. |
| | |
| | 2} LOCATE THE DISCONNECT FOR THE GUEST HOUSE ON THE |
| | PLAN AT THE UNIT. 225.31 |
| | |
| | 3} THE DISCONNECTS SHOWN ON THE RISER DIAGRAM ARE NOT |
| | LOCATED ON THE PLAN. 225.31 |
| | |
| | 4} COMMENT #7 FROM THE PREVIOUS REVIEW "7} CIRCUIT # 7, |
| | 9 IN PANEL "A" INDICATES LAUNDRY @ 1500 VA ON A SINGLE |
| | POLE BREAKER. CLARIFY WHAT THIS FEEDS"***THIS CIRCUIT |
| | NOW SAYS "WASHER" BUT STILL HAS TWO CIRCUITS ON A |
| | SINGLE POLE BREAKER.. |
| | |
| | 5} THE INSTA HOTS DO NOT HAVE THE OCP AMPERAGE PER |
| | MANUFACTURERS SPECS.110.26(B). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |