| 2008-12-31 15:04:49 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) FLAT ROOF ASSEMBLY TO BE INSTALLED. |
| | ***NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL SPECIFIC |
| | APPROVED ASSEMBLY TO BE USED AND SPECIFIC BASE SHEET |
| | FASTENING OPTION. ALSO, PROVIDE RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7. IF THOSE |
| | CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED, THEN |
| | PROVIDE THEM SIGNED AND SEALED. SEE GENERAL LIMITATION |
| | #7 ON LAST PAGE OF PRODUCT APPROVAL. ( NOTE: APPROVED |
| | ASSEMBLY WITH GENERAL LIMITATION #9 MAY NOT BE USED IN |
| | THIS PROJECT. CHECK THE UPLIFT PRESSURES). |
| | |
| | B) SHUTTERS AND COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. |
| | ALSO, MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING |
| | CONDITIONS (EG: WALL MOUNT, BUILD OUT, ETC) AND ANCHOR |
| | TYPE AND SPACING TO BE USED). |
| | |
| | C) SOLID SWING DOORS AS SHOWN ON PLANS. |
| | |
| | D) WINDOW MULLIONS. AND CLEARLY MARK ON DRAWINGS |
| | SPECIFIC MULLION SIZE AND ANCHOR TO BE USED TO VERIFY |
| | COMPLIANCE WITH PRODUCT APPROVAL AND CALCULATED DESIGN |
| | PRESSURES OF SEC. R301. |
| | |
| | E) FRENCH DOORS AS SHOWN ON PLANS. PRODUCT APPROVAL |
| | FL11146 SUBMITTED IS FOR 2007 CODE VERSION. NEED 2004 |
| | CODE VERSION. |
| | ALSO, NOA 08-0506.01 SUBMITTED IS FOR SMALL MISSILE |
| | IMPACT. NEED LARGE MISSILE IMPACT PROTECTION AS |
| | REQUIRED BY SEC. R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. FL10456 SUBMITTED IS FOR 2007 CODE |
| | VERSION. NEED TO PROVIDE ONE FOR CURRENT 2004 CODE |
| | VERSION. |
| | |
| | G) SINGLE HUNG WINDOWS. FL11633 SUBMITTED IS FOR 2007 |
| | CODE VERSION. NEED TO PROVIDE 2004 CODE VERSION. |
| | ALSO, NOA 08-0527.14 SUBMITTED IS FOR SMALL MISSILE |
| | IMPACT. NEED TO PROVIDE ONE FOR LARGE MISSILE IMPACT AS |
| | REQUIRED BY SEC. R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 3- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- AFTER DRAWINGS ARE REVISED, BRING THEM TO HISTORIC |
| | DISTRICT PLANNER TO GET APPROVAL STAMP. |
| | |
| | 5- SPECIFY SLOPE FOR FLAT ROOF TO VERIFY COMPLIANCE |
| | WITH SEC. R905.9.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6 PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.0 FBC 2004. |
| | ***NOTE: MAKE SURE CORRECT REVISED FORM IS USED AND ALL |
| | INFORMATION IS PROVIDED. ALSO, MAKE SURE OWNER/AGENT |
| | ALSO SIGNS AND DATES BOTTOM OF FORM. |
| | |
| | 7- OWES $0.38 FOR RADON FEES. |
| | |
| | 8- SINGLE HUNG 24 WINDOWS SPECIFIED ON PLANS DON'T |
| | COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310.1.2 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED. |
| | |
| | 9- SPECIFY THE DESIGN PRESSURES FOR ALL OPENINGS AS |
| | REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- PROVIDE SPECIFICATIONS IN PLANS AND WALL SECTIONS |
| | TO SHOW COMPLIANCE WITH THE 2 LAYERS OF WATER VAPOR |
| | BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 11- SHEET A-1: |
| | A) ROOF FRAMING PLAN: *SPECIFY NEW GIRDER TO CARRY THE |
| | ROOF JOISTS. AND SPECIFY POSTS TO SUPPORT IT AT BOTH |
| | ENDS. SEE FLOOR PLAN ON SHEET A-2 BY NEW KITCHEN AREA. |
| | IT CALLS FOR "NEW GIRDER FOR NEW 12" RAISED ROOF". |
| | ** PROVIDE DETAIL SHOWING HOW CONNECTING THE NEW ROOF |
| | JOISTS TO THE NEW GIRDER. CONNECTOR B1 IS A STRAP. NEED |
| | TO PROVIDE JOIST HANGER. SEE COMMENTS ON PLANS. |
| | |
| | B) UPDATE GENERAL NOTES AND FOUNDATION NOTES TO REFER |
| | TO THE 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS, NOT 2006. |
| | |
| | C) REVISE ROOF FRAMING NOTES. ROOF FRAMING PLAN DOESN'T |
| | SPECIFY ROOF TRUSSES. |
| | |
| | 12- SHEET A-2: |
| | A) REVISE LOCATION OF NEW ATTIC ACCESS FOR ACCESSORY |
| | BUILDING AND MAIN BUILDING TO SHOW COMPLIANCE WITH |
| | HEADROOM REQUIREMENTS OF SEC. R807 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 13- SHEET DT-1: |
| | A) TYP. INTERIOR WALL SECTION 7: CLARIFY IF FRAMING IS |
| | WOOD STUDS OR METAL STUDS. IT CALLS FOR 2X4 STUDS, BUT |
| | METAL CHANEL BOTTOM SILL. |
| | |
| | B) NEW WALL DETAIL 3 AND STEM WALL DETAIL CALL FOR |
| | ATTACHMENT OF 2X8 SILL TO CONCRETE SLAB. DRAWINGS DON'T |
| | SHOW CONCRETE SLAB, BUT CONCRETE BLOCK. REVISE AS |
| | REQUIRED TO CLARIFY. |
| | |
| | C) SECTION 5: REVISE ROOF SHEATHING NAIL SPACING. NEED |
| | TO BE 4"O.C. AT ROOF ZONE 3# AS REQUIRED BY SEC. |
| | R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS |
| | REQUIRED. |
| | |
| | D) SPECIFY HEADER SIZE FOR WINDOW OPENING ON DETAIL A. |
| | PLANS DON'T SPECIFY HEADER. |
| | |
| | E) WINDOW SILL SPECIFICATIONS SHOWN ON DETAIL A DON'T |
| | MATCH THOSE SHOWN ON DETAIL B. REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |