Plan Review Notes
Plan Review Notes For Permit 08120242
Permit Number 08120242
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-31 15:04:49RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FLAT ROOF ASSEMBLY TO BE INSTALLED.
 ***NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL SPECIFIC
 APPROVED ASSEMBLY TO BE USED AND SPECIFIC BASE SHEET
 FASTENING OPTION. ALSO, PROVIDE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7. IF THOSE
 CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED, THEN
 PROVIDE THEM SIGNED AND SEALED. SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF PRODUCT APPROVAL. ( NOTE: APPROVED
 ASSEMBLY WITH GENERAL LIMITATION #9 MAY NOT BE USED IN
 THIS PROJECT. CHECK THE UPLIFT PRESSURES).
  
 B) SHUTTERS AND COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
 ALSO, MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EG: WALL MOUNT, BUILD OUT, ETC) AND ANCHOR
 TYPE AND SPACING TO BE USED).
  
 C) SOLID SWING DOORS AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS. AND CLEARLY MARK ON DRAWINGS
 SPECIFIC MULLION SIZE AND ANCHOR TO BE USED TO VERIFY
 COMPLIANCE WITH PRODUCT APPROVAL AND CALCULATED DESIGN
 PRESSURES OF SEC. R301.
  
 E) FRENCH DOORS AS SHOWN ON PLANS. PRODUCT APPROVAL
 FL11146 SUBMITTED IS FOR 2007 CODE VERSION. NEED 2004
 CODE VERSION.
 ALSO, NOA 08-0506.01 SUBMITTED IS FOR SMALL MISSILE
 IMPACT. NEED LARGE MISSILE IMPACT PROTECTION AS
 REQUIRED BY SEC. R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. FL10456 SUBMITTED IS FOR 2007 CODE
 VERSION. NEED TO PROVIDE ONE FOR CURRENT 2004 CODE
 VERSION.
  
 G) SINGLE HUNG WINDOWS. FL11633 SUBMITTED IS FOR 2007
 CODE VERSION. NEED TO PROVIDE 2004 CODE VERSION.
 ALSO, NOA 08-0527.14 SUBMITTED IS FOR SMALL MISSILE
 IMPACT. NEED TO PROVIDE ONE FOR LARGE MISSILE IMPACT AS
 REQUIRED BY SEC. R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 3- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- AFTER DRAWINGS ARE REVISED, BRING THEM TO HISTORIC
 DISTRICT PLANNER TO GET APPROVAL STAMP.
  
 5- SPECIFY SLOPE FOR FLAT ROOF TO VERIFY COMPLIANCE
 WITH SEC. R905.9.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6 PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.0 FBC 2004.
 ***NOTE: MAKE SURE CORRECT REVISED FORM IS USED AND ALL
 INFORMATION IS PROVIDED. ALSO, MAKE SURE OWNER/AGENT
 ALSO SIGNS AND DATES BOTTOM OF FORM.
  
 7- OWES $0.38 FOR RADON FEES.
  
 8- SINGLE HUNG 24 WINDOWS SPECIFIED ON PLANS DON'T
 COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310.1.2 OF
 2004 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED.
  
 9- SPECIFY THE DESIGN PRESSURES FOR ALL OPENINGS AS
 REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 10- PROVIDE SPECIFICATIONS IN PLANS AND WALL SECTIONS
 TO SHOW COMPLIANCE WITH THE 2 LAYERS OF WATER VAPOR
 BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 11- SHEET A-1:
 A) ROOF FRAMING PLAN: *SPECIFY NEW GIRDER TO CARRY THE
 ROOF JOISTS. AND SPECIFY POSTS TO SUPPORT IT AT BOTH
 ENDS. SEE FLOOR PLAN ON SHEET A-2 BY NEW KITCHEN AREA.
 IT CALLS FOR "NEW GIRDER FOR NEW 12" RAISED ROOF".
 ** PROVIDE DETAIL SHOWING HOW CONNECTING THE NEW ROOF
 JOISTS TO THE NEW GIRDER. CONNECTOR B1 IS A STRAP. NEED
 TO PROVIDE JOIST HANGER. SEE COMMENTS ON PLANS.
  
 B) UPDATE GENERAL NOTES AND FOUNDATION NOTES TO REFER
 TO THE 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS, NOT 2006.
  
 C) REVISE ROOF FRAMING NOTES. ROOF FRAMING PLAN DOESN'T
 SPECIFY ROOF TRUSSES.
  
 12- SHEET A-2:
 A) REVISE LOCATION OF NEW ATTIC ACCESS FOR ACCESSORY
 BUILDING AND MAIN BUILDING TO SHOW COMPLIANCE WITH
 HEADROOM REQUIREMENTS OF SEC. R807 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 13- SHEET DT-1:
 A) TYP. INTERIOR WALL SECTION 7: CLARIFY IF FRAMING IS
 WOOD STUDS OR METAL STUDS. IT CALLS FOR 2X4 STUDS, BUT
 METAL CHANEL BOTTOM SILL.
  
 B) NEW WALL DETAIL 3 AND STEM WALL DETAIL CALL FOR
 ATTACHMENT OF 2X8 SILL TO CONCRETE SLAB. DRAWINGS DON'T
 SHOW CONCRETE SLAB, BUT CONCRETE BLOCK. REVISE AS
 REQUIRED TO CLARIFY.
  
 C) SECTION 5: REVISE ROOF SHEATHING NAIL SPACING. NEED
 TO BE 4"O.C. AT ROOF ZONE 3# AS REQUIRED BY SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS
 REQUIRED.
  
 D) SPECIFY HEADER SIZE FOR WINDOW OPENING ON DETAIL A.
 PLANS DON'T SPECIFY HEADER.
  
 E) WINDOW SILL SPECIFICATIONS SHOWN ON DETAIL A DON'T
 MATCH THOSE SHOWN ON DETAIL B. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712