| 2009-05-01 16:22:26 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. LETTER STATES THAT THAT BLOCK MAY PROTRUDE A MINIMUM |
| | OF 1"; PLEASE REVISE TO STATE "MAXIMUM" OR EXPLAIN |
| | RATIONALE. |
| | |
| | 2. PLEASE PROVIDE JUSTIFICATION FOR THE STATEMENT THAT |
| | THIS IS "WITHOUT STRUCTURAL COMPROMISE." CALCULATIONS |
| | WERE PROVIDED FOR THE FOUNDATION SIZE; AREN'T THOSE |
| | CALCULATIONS BASED ON THE BLOCK BEARING ON THE CENTER |
| | OF THE FOUNDATION? PLEASE PROVIDE MORE INFORMATION |
| | REGARDING HOW THIS CHANGE IN DESIGN WILL AFFECT THE |
| | STRUCTURAL INTEGRITY. THIS MAY BE ACCOMPLISHED IN PART |
| | BY TELEPHONING ROBERT BROWN, ASSISTANT BUILDING |
| | OFFICIAL, 561-805-6652. |
| | |
| | 3. ONE COMMENT FROM THE HOUSE (09020075) PLAN REVIEW |
| | WAS NOT ADDRESSED: |
| | |
| | PROVIDE FOUNDATION VENTING SPECIFICATION FBC R408.1. |
| | |
| | THE HYDROVENT CALCULATIONS WERE PROVIDED, BUT UNDER |
| | FLOOR VENTILATION WAS NOT ADDRESSED. THE PLAN PROVIDED |
| | DOES NOT SHOW DIMENSIONED LOCATIONS AND, WHEN SCALED, |
| | DO NOT COMPLY WITH FBC R408.1. PLEASE CLARIFY LOCATION |
| | FOR VENTILATION IN THE REVISED LETTER. |
| | |
| | |
| | . |