| Plan Review Notes For Permit 08120208 |
| Permit Number |
08120208 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-18 15:51:07 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | REQUIREMENT FOR THE GROUNDING ELECTRODE SYSTEM: | | | | | | 250.52(A)(3) CONCRETE-ENCASED ELECTRODE -AN ELECTRODE | | | ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED | | | WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR | | | FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, | | | CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE | | | BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY | | | CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT | | | LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING | | | OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT | | | SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED | | | TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR | | | OTHER EFFECTIVE MEANS. | | | | | | GIVEN THAT THE FOOTER MAY BE POURED WITHOUT THE | | | ELECTRICAL CONTRACTORS KNOWLEDGE, THIS GROUNDING | | | ELECTRODE CONDUCTOR, INSTALLED AND SIZED PER 250.66, | | | MUST BE INSTALLED AT THIS STAGE OF THE WORK. INDICATE | | | SIZE AND LOCATION ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|