Plan Review Notes
Plan Review Notes For Permit 08120196
Permit Number 08120196
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-24 09:39:37DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 EXISTING
  
 1. SHT AO-O BUILLDING CODES INDICATED AS 1997 STANDARD
 BUILDING CODE. CODE CRITERIA SHALL BE FBC-2004 WITH
 2007 REVISIONS.
  
 2. INDICATE LEVEL OF ALTERATION PER CHAPTER 3 OF THE
 EXISTING BUILDING CODE.
  
 3. CITY PLACE APPROVAL NOT COMPLETE FOR EACH SHEET.
 (NOT INITIALED).
  
 4. SHT P0.1 IDENTIFY FITTINGS AT THE TOP OF THE DROP
 FOR THE WATER LINES ON THE WATER ISOMETRIC RISER
 DIAGRAM. IF THEY ARE AIR CHAMBERS THEN THEY ARE NOT
 APPROVED AND SHALL BE DELETED. SECTION 604.9. IF THEY
 ARE WATER HAMMER ARRESTORS, THEN THEY SHALL BE
 INSTALLED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING. PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  