| Plan Review Notes For Permit 08120196 |
| Permit Number |
08120196 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-24 09:39:37 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 EXISTING | | | | | | 1. SHT AO-O BUILLDING CODES INDICATED AS 1997 STANDARD | | | BUILDING CODE. CODE CRITERIA SHALL BE FBC-2004 WITH | | | 2007 REVISIONS. | | | | | | 2. INDICATE LEVEL OF ALTERATION PER CHAPTER 3 OF THE | | | EXISTING BUILDING CODE. | | | | | | 3. CITY PLACE APPROVAL NOT COMPLETE FOR EACH SHEET. | | | (NOT INITIALED). | | | | | | 4. SHT P0.1 IDENTIFY FITTINGS AT THE TOP OF THE DROP | | | FOR THE WATER LINES ON THE WATER ISOMETRIC RISER | | | DIAGRAM. IF THEY ARE AIR CHAMBERS THEN THEY ARE NOT | | | APPROVED AND SHALL BE DELETED. SECTION 604.9. IF THEY | | | ARE WATER HAMMER ARRESTORS, THEN THEY SHALL BE | | | INSTALLED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", | | | NOT IN THE CEILING. PDI-WH 201. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|