| Plan Review Notes For Permit 08120196 |
| Permit Number |
08120196 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-16 14:19:18 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE | | | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE | | | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE | | | ARTICLE. PUT A NOTE ON THE PLAN FOR CLARITY IN THE | | | FIELD. SHEET E0.1 | | | | | | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 | | | FBC AS AMENDED.SEE SHEET AO-O REFERENCING 1997 STANDARD | | | BUILDING CODE. | | | | | | 3} ALL WORK DONE AT CITY PLACE REQUIRES THE PRE | | | APPROVAL OF THE MANAGEMENT OFFICE AND ALTHOUGH THE | | | STAMP IS ON THE PLANS, IT NEEDS TO BE INITIALED BY THE | | | MANAGEMENT PER RAY KEATS. | | | | | | NOTE: PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR | | | REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE | | | REMOVED FOR DEMOLITION.NO ELECTRICAL CONTRACTOR IS | | | SIGNED ON THE APPLICATION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|