Plan Review Notes
Plan Review Notes For Permit 08120196
Permit Number 08120196
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-16 14:19:18 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. PUT A NOTE ON THE PLAN FOR CLARITY IN THE
 FIELD. SHEET E0.1
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.SEE SHEET AO-O REFERENCING 1997 STANDARD
 BUILDING CODE.
  
 3} ALL WORK DONE AT CITY PLACE REQUIRES THE PRE
 APPROVAL OF THE MANAGEMENT OFFICE AND ALTHOUGH THE
 STAMP IS ON THE PLANS, IT NEEDS TO BE INITIALED BY THE
 MANAGEMENT PER RAY KEATS.
  
 NOTE: PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION.NO ELECTRICAL CONTRACTOR IS
 SIGNED ON THE APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  