| 2009-05-27 14:55:13 | **DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | AT A MINIMUM. 2ND REQUEST. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA- 72 |
| | THE ELECTRICAL PLANS DO NOT STATE ANY CODES. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH |
| | RESPECT TO PERMIT APPLICATION. THERE IS NOW A STATEMENT |
| | ON PERMIT APPLICATION WHICH STATES * FEE SIMPLE TOWN |
| | HOUSES*. HOWEVER IF THESE ARE INDEED FEE SIMPLE THEN |
| | SEPARATE PERMIT APPLICATION, SITE/SURVEY, PLANS, |
| | SEPARATE FEES ETC WOULD BE REQUIRED FOR EACH UNIT ALONG |
| | WITH NEW ADDRESSES FOR EACH. |
| | ** PLANS ON THE OTHER HAND INDICATE THIS AS A |
| | MULTI-UNIT BUILDING. |
| | ** IF THIS IS A MULTI-UNIT BUILDING AS MULTI-FAMILY, OR |
| | CONDO TYPE THEN NO SEPARATE METER SERVICE IS PERMITTED |
| | FOR EACH UNIT. THIS CAN ONLY HAVE ONE SERVICE. |
| | IF THIS IS FEE SIMPLE AS STATES ALL MUST BE UNDER |
| | SEPARATE PERMITS. |
| | IT IS IMPORTANT TO KEEP IN MIND THAT ANY CHANGE IN THE |
| | ADOPTED CURRENT CODES WOULD AFFECT ALL UNITS NOT |
| | APPLIED FOR PERMIT BEFORE THE ADOPTION OF ANY NEW |
| | CODES. |
| | THE BUILDING CODE HAS SINCE CHANGED FROM THE ORIGINAL |
| | PERMIT APPLICATION AS OF MARCH 1ST, 2009. |
| | THE BUILDING MAY NOT BE *MASTERED* AS ALL PERMIT |
| | APPLICATION MUST BE MADE BEFORE CODE CHANGES. PLEASE |
| | KNOW THAT THE ELECTRICAL CODE MAY ALSO BE CHANGING TO |
| | THE 2008 NFPA-70 IN THE NEXT COUPLE OF MONTHS. THIS |
| | WILL GREATLY AFFECT THE DESIGN. |
| | |
| | ** ALL OF THE ABOVE WAS NOTED ON THE PREVIOUS REVIEW |
| | WITH RESPECT TO THE CODE CHANGING. |
| | ** BASED ON NO PERMIT APPLICATIONS MADE TO AN *FEE |
| | SIMPLE UNITS*, THE DESIGN WILL NOW FALL UNDER THE NEXT |
| | CODE CYCLE. |
| | 2007 FBC W/ 2009 REVISION. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ALL |
| | INFORMATION REQUIRED ON TITLE BLOCKS PER FAC |
| | 61G1-16.004. PLEASE ALSO INCLUDE ADDRESS SPECIFIC TO |
| | EACH LOCATION ONCE ADDRESS HAS BEEN DETERMINED. PLEASE |
| | KNOW THAT THE ADDRESSING CAN NOT BE CONFIRMED AS THE |
| | APPLICATION AND PLANS ARE NOT CLEAR WITH RESPECT TO |
| | WHAT TYPE OF PERMIT/BUILDING THIS IS ACTUALLY BE. |
| | FBC 106.1.1,106.1.2,106.3.5.1.2,106.5. |
| | NEC, 220 ,240 , 210, 230 .310.16 ETC |
| | |
| | 4) NOTE: RISER STATES *(BUILDING STEEL). IS THIS MEANT |
| | TO BE *FOOTER STEEL*? PER 250.50 THERE ARE TWO METHODS |
| | OR LOCATIONS. STRUCTURE COULD HAVE BUILDING STEEL AS |
| | WELL AS FOOTER STEEL. |
| | |
| | 5) NOTE: PLEASE SEE THE MINIMUM VA FOR LAUNDRY/WASHER |
| | CIRCUIT SHALL BE 1500VA MINIMUM PER 220.52. |
| | CALCULATIONS ONLY INDICATE 1200VA |
| | |
| | 6) NOTE: PLEASE SEE PLANS WHICH INDICATE A METER AND A |
| | MAIN DISCONNECT OUTSIDE HOWEVER THE RISER DOES NOT |
| | INDICATE ANY MAIN OUTSIDE? |
| | PLEASE SEE PREVIOUS NOTES AND THIS NOTE REPEATED AS |
| | THERE CAN BE NO MORE THAN 8FT OF UNPROTECTED CONDUCTORS |
| | INSIDE THE BUILDING. |
| | PLEASE SEE 230.70, 230.71, 230.72 ETC. |
| | THIS MAY CHANGE BASED ON THE TYPE OF BUILDING IN WHICH |
| | IS WILL BECOME. IT IS RECOMMENDED THAT IF THERE ARE |
| | QUESTIONS ON THIS TO PLEASE CALL. |
| | |
| | 7) NOTE: FROM PREVIOUS NOTES, DEPENDING ON THE ACTUAL |
| | SERVICE IT CAN BE DETERMINED AT THIS TIME WHAT TYPE OF |
| | ELECTRICAL SERVICE WILL BE NEEDED. |
| | |
| | 8) NOTE: PREVIOUS REVIEW COMMENT: SHOW ALL CONTINUOUS |
| | LOADS AT 125% PER 422.13. THE 2005 NEC WAS UPDATED TO |
| | CHANGE THIS. PLEASE READY COMMENTARY AT 422.13. |
| | |
| | 10) NOTE: PLEASE SEE 422.17 FROM PREVIOUS REVIEW. THE |
| | PLANS WERE UPDATED TO INCLUDE A NOTE HOWEVER KEEP IN |
| | MIND THE CODE REQUIRES MINIMUM CLEARANCE. THE NOTE ON |
| | PLANS SIMPLY STATES NOT AGAINST EQUIPMENT WHICH IS NOT |
| | ADEQUATE. |
| | |
| | 11) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | CIRCUITING THE BREAKFAST AREA/DINING ROOM RECEPTACLES. |
| | PLEASE SEE 210.52B1,210.11C1,220.52 FOR ONE OR MORE |
| | SMALL APPLIANCE CIRCUITS. WHERE IS BREAKFAST OR DINING |
| | ARE BEING FED FROM? |
| | |
| | 12) NOTE: PLEASE SEE THE ELECTRICAL PANEL SCHEDULE ONLY |
| | INDICATES 15AMP 2-POLE FOR AIR HANDLER UNIT HOWEVER |
| | BASED ON THE MECHANICAL PLANS THE SIZE OF THE UNIT IS |
| | MUCH GREATER. IN FACT THE *MINIMUM* CIRCUIT AMPACITY IS |
| | 60AMPS. PLEASE ALSO SEE THE M SHEETS STATES 10KW HEAT |
| | YET TH ELECTRICAL CALCULATIONS DO NOT INDICATE THIS |
| | LOAD. THE LOAD SHOWN IS WAY UNDER 10KW ON ELECTRICAL |
| | PLANS. |
| | 424.3B, 310.16,220.80,220.60 ETC |
| | |
| | 13) NOTE: IF PLANS ARE SET FOR MULTI-RESIDENTIAL |
| | BUILDING AS SHOWN. PLEASE BE SURE ALL CIRCUITING IS |
| | COMPLETED ON PLANS AND COORDINATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. EACH UNIT WOULD BE SPECIFIC UNDER THE |
| | 2005 NEC 408.4. |
| | |
| | 14) NOTE: PLANS DO NOT INDICATE ANY NOTES FROM FBC |
| | 13-606.1.ABC.1.2.4 WITH RESPECT TO TYPE OF RECESSED |
| | LIGHTING FIXTURES REQUIRED. |
| | |
| | 15) NOTE: PLANS INDICATES ON RISER A *#8* GROUND ROD. |
| | WHAT IS A #8 GROUND ROD? |
| | PLEASE SEE MINIMUM REQUIRED GROUNDING ELECTRODE PER |
| | 250.52A5,220.53 ETC |
| | |
| | 16) NOTE: PLANS ARE STILL MISSING SOME RECEPTACLES PER |
| | 210.52. SOME EXAMPLES WERE GIVEN IN THE PREVIOUS REVIEW |
| | HOWEVER NOT ALL LOCATIONS WERE IDENTIFIED. |
| | |
| | 17) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |