| 2009-01-12 16:42:25 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 (ADMIN) |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT T-1 PLUMBING NOTES: |
| | #2, 2-1/2" AND LESS 1/4" PER LINEAR FOOT SLOPE |
| | REQUIRED. TABLE 704.1. |
| | #5 FBC-2004 WITH 2007 AMENDMENTS IS THE CODE ADOPTED. |
| | THE SOUTH FLORIDA BUILDING CODE WAS FOR BROWARD AND |
| | DADE COUNTIES ONLY AND THE FLORIDA BUILDING CODE HAS |
| | BEEN IN EFFECT SINCE THE 2001 VERSION WHICH WENT INTO |
| | EFFECT ON MARCH 1, 2003. |
| | #8 AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | REFERENCE. SECTION 604.9. |
| | |
| | 2. ALL SHEETS WITH THE BENEDICT GROUP ARCHITECTURE & |
| | PLANNING. THE PRINTED NAME OF THE PERSON SEALING THE |
| | PLANS IS REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC |
| | 61G1-16.004(6) & FS 481.2055. |
| | |
| | 3. ALL SHEETS WITH THE BENEDICT GROUP ARCHITECTURE & |
| | PLANNING. THE SIGNATURE OF THE ARCHITECT SHALL APPEAR |
| | ON ALL ARCHITECTURAL DOCUMENTS TO BE FILED FOR PUBLIC |
| | RECORD. IT APPEARS THAT INITIALS WERE USED. IF THIS IS |
| | INDEED THE LEGAL SIGNATURE OF THE ARCHITECT OF RECORD, |
| | THEN A SIGNED, SEALED, NOTORIZED LETTER INDICATING THE |
| | LEGAL SIGNATURE SHALL BE SUBMITTED TO THIS OFFICE FOR |
| | OUR RECORD. FAC 61G1-16.003, 61G1-16.004(5) AND FS |
| | 481,2055. |
| | |
| | 4. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 PLUMBING NOTES: |
| | #2, 2-1/2" AND LESS 1/4" PER LINEAR FOOT SLOPE |
| | REQUIRED. TABLE 704.1. |
| | #5 FBC-2004 WITH 2007 AMENDMENTS IS THE CODE ADOPTED. |
| | THE SOUTH FLORIDA BUILDING CODE WAS FOR BROWARD AND |
| | DADE COUNTIES ONLY AND THE FLORIDA BUILDING CODE HAS |
| | BEEN IN EFFECT SINCE THE 2001 VERSION WHICH WENT INTO |
| | EFFECT ON MARCH 1, 2003. |
| | #8 AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | REFERENCE. SECTION 604.9. |
| | |
| | 5. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 NOTE STATES VTR'S |
| | SHALL MERGE TO ONE VTR BEFORE IT TERMINATES OFF THE |
| | ROOF. EXCEPT LAUNDRY VENT. PLEASE SHOW THE PIPING ON |
| | THE ISOMETRIC SANITARY RISER DIAGRAM. SHOW ALL PIPE |
| | SIZES OF VENTS. SECTIONS 106.1.1 & TABLE 916.1. |
| | |
| | 6. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 EXPLAIN THE FLOOR |
| | DRAIN FOR THE WATER HEATER. SECTION 106.1.2. A TRAP |
| | PRIMER MAY BE REQUIRED PER SECTION 1002.4. |
| | |
| | 7. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 WATER HEATER |
| | DETAIL. THE P/T DISCHARGE PIPE SHALL HAVE NOT TRAPPED |
| | SECTIONS AND SHALL HAVE AN AIR GAP OR AIR GAP FITTING |
| | IN THE SAME ROOM PER SECTION 504.6.1. PLEASE INDICATE |
| | HOW THE P/T LINE WILL BE RUN TO THE OUTSIDE FROM THE |
| | INTERIOR UNITS. SECTION 106.1.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |