| 2009-01-02 11:37:40 | ** DENIED REVIEW ** |
| | |
| | ** IMPORTANT** |
| | AS THERE IS SOME INFORMATION OR ITEMS NOT YET SUBMITTED |
| | FOR CODE COMPLIANCE THERE MAY VERY WELL BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| | TIME. PLEASE ALSO BE WARE THAT SOME OF THE COMMENTS |
| | BELOW WILL CASE REVISIONS TO PLANS WHICH SOMETIMES |
| | CREATE NEW COMMENTS. |
| | |
| | 1) NOTE: PLEASE KNOW ONCE THE ADDRESS OF EACH FEE |
| | SIMPLE UNIT IS DONE AND COMPLETED, EACH SET OF PLANS |
| | FOR EACH PERMITTED TOWN HOUSE WILL BE REQUIRED TO BE |
| | ADDRESSED INCLUDING THE ADDRESS ON THE TITLE BLOCKS. |
| | THE ADDRESSES FOR EACH HAS YET TO BE CONFIRMED AND THIS |
| | WILL BE DONE BY THE BUILDING AND ADDRESSING REVIEWER. |
| | THE PERMIT APPLICATION AS SUBMITTED WAS FOR ONE 5 UNIT |
| | BUILDING HOWEVER THIS PERMIT HAS AN APPLIED VALUE FOR |
| | ONE UNIT ONLY. ONCE ALL FINAL APPLICATIONS AND |
| | ADDRESSES HAVE BEEN CONFIRMED PLEASE BE SURE PLANS ARE |
| | COORDINATED. |
| | FAC61G1-16.004 |
| | FBC 106.5 |
| | |
| | 2) NOTE: PLEASE SEE FAC 61G1-16.004, AS THE TITLE |
| | BLOCKS FOR THE ARCHITECTURAL FIRM IS MISSING THE |
| | REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF |
| | SAID DESIGNER. THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | AL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | |
| | 3) NOTE: PLEASE BE SURE PLANS CONTAIN THE FOLLOWING |
| | CODES. SOME ARE ALREADY SHOWN HOWEVER THESE ARE |
| | REQUIRED FOR THIS REVIEWER. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | *** PLEASE KEEP IN MIND ALL PERMIT APPLICATIONS FOR ALL |
| | UNITS MUST BE APPLIED FOR BEFORE MARCH 1ST, 2009 |
| | OTHERWISE ANY PERMIT APPLICATIONS AFTER THIS DATE WILL |
| | ALL FOR UNDER THE NEW CODES COMING INTO AFFECT BY THE |
| | STATE OF FLORIDA. PLEASE ALSO BE AWARE OF CHANGES IN |
| | THE NEC/NFPA-70 WHICH WILL ALSO BE CHANGING COMING UP |
| | IN MONTHS TO COME. |
| | |
| | 4) NOTE: PLEASE SEE 210.52D AS THE GFI SHOWN ON THE |
| | FIRST LEVEL BATH ROOM SHALL BE PLACED IN THE MIDDLE |
| | BETWEEN THE TWO SINKS OR A SECOND DEVICE WILL BE |
| | REQUIRED TO BE ADDED. AN OCCUPANT MAY NOT CROSS OVER |
| | ONE SINK TO PLUG IN ANY APPLIANCE. |
| | |
| | 5) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE |
| | WATER HEATER LOAD IS NOW CONSIDERED A CONTINUOUS LOAD |
| | AND NEEDS TO BE SHOWN AT 125%. |
| | THE PREVIOUS CODE REQUIRED THE SIZING FROM BRANCH |
| | CIRCUIT AND WIRING TO BE AT 125%, HOWEVER THE NEW |
| | CHANGE IS TO CARRY THE 125% LOAD FOR SIZING FEEDERS AND |
| | SERVICE. |
| | PLEASE ADJUST PLANS. |
| | |
| | 6) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR |
| | REQUIRED LOADS ON CIRCUITS FOR SMALL APPLIANCES, DINING |
| | AND BREAKFAST ROOM. THE OTHER TWO LOCATIONS CAN NOT BE |
| | CONFIRMED DUE TO NO CIRCUITING BEING SHOWN ON THE PLANS |
| | AT THIS TIME. |
| | PLEASE KNOW THAT THE ONE OR *MORE* CIRCUITS REQUIRE THE |
| | 1.5KVA. THE LOADS SHOWN ON PANEL SCHEDULE FOR DINING |
| | ROOM ARE WELL BELOW THE REQUIRED MINIMUM OF 1500VA. |
| | |
| | 7) NOTE: PLEASE SUBMIT AND INDICATE THE AIC RATING FOR |
| | ALL SERVICE EQUIPMENT PER 110.9. |
| | |
| | 8) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCE |
| | REQUIREMENTS OF THE A/C DISCONNECT FOR THE CONDENSING |
| | UNIT. AS SHOWN ON THE PLANS THIS DISCONNECT IS BEHIND |
| | THE UNIT WHICH DOES NOT MEET MINIMUM CLEARANCES. |
| | |
| | 9) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTION |
| | OF ALL 15/20AMP 120V RECEPTACLES WITHIN 6FT OF A |
| | LAUNDRY SINK. THIS WAS A CHANGE IN THE 2005 NEC AND IS |
| | REQUIRED EVEN FOR DEDICATED CIRCUITS SUCH AS THE WASHER |
| | CIRCUIT. |
| | |
| | 10) NOTE: RISER IS SHOWING AN EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE METER TO THE MAIN BREAKER PANEL |
| | WHICH IS NOT PERMITTED. THE CONDUCTOR IS ALSO SHOWN |
| | AS#5. THERE NO SUCH CONDUCTOR SIZE BASED ON THE AWG |
| | (AMERICAN WIRE GAUGE). |
| | PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO MAIN |
| | SHOWN ON PLANS. THIS WILL AFFECT THIS COMMENT. |
| | 250.6,250.24,250.110, ETC SIZE PER 250.122. |
| | |
| | 11) NOTE: PLEASE COORDINATE RISER AND PLANS. THE RISER |
| | DOES NOT SHOW A MAIN DISCONNECT OUTSIDE YET THE PLANS |
| | DO SHOW A MAIN NEXT TO THE METER. |
| | PLEASE ALSO SEE THE PLANS DO NOT SHOW THE ELECTRICAL |
| | PANEL LOCATION. 240.24,110.26 ETC |
| | PLEASE COORDINATE AND PLEASE SEE 230.70,230.71 AS NO |
| | MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED |
| | INSIDE THE BUILDING. |
| | FBC 106.1.1 FOR CLARITY OF PLANS AND COORDINATION. |
| | |
| | 12) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| | SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| | SMOKE DETECTORS. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 AND THE FLORIDA |
| | BUILDING CODE A SD/ SMOKE DETECTOR IS ONLY A DEVICE |
| | WHICH WILL DETECT AND WILL NOT SOUND AN AUDIBLE ALARM. |
| | THIS WOULD BE DONE BY HORN/SIREN TYPE DEVICES. |
| | PLEASE SEE THE DEFINITIONS OF SA/SMOKE ALARMS; THESE |
| | ARE DEVICES WHICH ARE 120V (AS SHOWN) AND WOULD DETECT |
| | AND SOUND AN ALARM. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. IF THESE ARE |
| | INDEED SMOKE DETECTORS, PLEASE SUBMIT COMPLETE PLANS |
| | SHOWING THE REQUIRED FIRE ALARM PANEL AND HORN/SOUNDING |
| | DEVICES. IF THESE ARE INDEED SMOKE ALARMS, PLEASE |
| | ADJUST DESIGNATIONS ON PLANS AND SYMBOL LEGEND. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3, R313 |
| | |
| | ** PLEASE SEE 11.8.3 ABOVE IN NFPA-72 AS THE SMOKE |
| | DEVICE IN THE MASTER BEDROOM IS REQUIRED TO BE LOCATED |
| | WITHIN 12 INCHES OF THE HIGHEST POINT OF CEILINGS. WHEN |
| | THERE ARE TRAY CEILINGS THIS MAY AFFECT THE LOCATION. |
| | BASED ON THE ARCHITECTURAL SHEET WHICH INDICATES THE |
| | CEILING DIFFERENCE OF ONLY 6INCHES THE LOCATION AS |
| | SHOWN IS OK AS LONG AS THERE ARE NO HEADERS INSTALLED |
| | AT OPENING. IF THE CEILING HEIGHT DOES CHANGE THIS MAY |
| | AFFECT THE LOCATION. |
| | |
| | 13) NOTE: PLANS SHOW BOTH DISPOSAL AND DISHWASHER ON |
| | SEPARATE RECEPTACLES WHICH IS OK HOWEVER PLEASE BE SURE |
| | TO SEE 210.4B. PLEASE VERIFY IF BOTH WILL BE ON THE |
| | SAME YOKE. IF SO THEN THIS WILL BE REQUIRED TO BE A |
| | 2-POLE BREAKER. THIS IS ONLY NOTED AS NO CHANGES ARE |
| | NEEDED AT THIS TIME. |
| | NEC 300, 210.4B |
| | FBC 106.1.1 FOR INFORMATION ONLY. |
| | |
| | 14) NOTE: PLEASE PROVIDE THE WORST CASE VOLTAGE DROP |
| | FOR FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED |
| | THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES |
| | A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END |
| | DEVICE ON A CIRCUIT. THIS MAY AFFECT FEEDERS OR BRANCH |
| | CIRCUIT CONDUCTORS. |
| | PLEASE SEE FBC13-413.1ABC.1. |
| | |
| | 15 ) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER |
| | 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN |
| | THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH |
| | DEPARTMENT OF COMMUNITY AFFAIRS. |
| | |
| | 16) NOTE: PLEASE INCLUDE TYPE OF RECESSED LIGHTING |
| | FIXTURES PER FBC 13-606.1.ABC.1.2.4 |
| | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT |
| | ABUT AN ATTIC SPACE SHALL MEET ONE OF THE FOLLOWING |
| | REQUIREMENTS: |
| | 1. TYPE IC RATED, MANUFACTURED WITH NO PENETRATIONS |
| | BETWEEN THE INSIDE OF THE RECESSED FIXTURE AND CEILING |
| | CAVITY AND SEALED OR GASKETED TO PREVENT AIR LEAKAGE |
| | INTO THE UNCONDITIONED SPACE. |
| | 2. TYPE IC OR NON-IC RATED, INSTALLED INSIDE A SEALED |
| | BOX [MINIMUM OF ?-INCH-THICK (12.7 MM)] GYPSUM WALL |
| | BOARD, PREFORMED POLYMERIC VAPOR BARRIER, OR OTHER AIR |
| | TIGHT ASSEMBLY MANUFACTURED FOR THIS PURPOSE) AND |
| | MAINTAINING REQUIRED CLEARANCES OF NOT LESS THAN |
| | ?-INCH-THICK (12.7 MM) FROM COMBUSTIBLE MATERIAL AND |
| | NOT LESS THAN 3 INCH (76 MM) FROM INSULATION MATERIAL. |
| | 3. TYPE IC RATED, WITH NO MORE THAN 2.0 CFM (.00094 |
| | M3/S) AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE |
| | CEILING CAVITY WHEN MEASURED IN ACCORDANCE WITH ASTM E |
| | 283. THE FIXTURE SHALL BE TESTED AT 75 PA AND SHALL BE |
| | LABELED. |
| | |
| | 17) NOTE: PLEASE SEE 410.8 FOR MINIMUM CLEARANCES |
| | REQUIRED FOR CLOSET LIGHTING FIXTURES. BASED ON THE |
| | PLANS THEY APPEAR TO INDICATE SHELVING RIGHT UP NEXT TO |
| | THE FIXTURE. PLEASE ADJUST LOCATION OF FIXTURES. SEE |
| | BEDRM #2 CLOSET FOR ONE EXAMPLE. |
| | |
| | 18) NOTE: PLEASE SEE 422.17 FOR WATER INSTALLATION |
| | LOCATION WHICH IS NOT PERMITTED TO HAVE COMBUSTIBLES |
| | STORED UP AGAINST UNIT. |
| | |
| | 19) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTER SPACE SHALL BE GFI OR GFI PROTECTED. |
| | SEE UNIT COUNTER WHICH IS MISSING GFI DESIGNATION. |
| | |
| | 20) NOTE: PLEASE SEE 210.52C1 FOR RECEPTACLES SPACING |
| | WHICH REQUIRES A GFI RECEPTACLE WITHIN 2FT OF THE END |
| | OF A COUNTER SPACE. THE COUNTER SPACE NEXT TO THE RANGE |
| | TOWARDS THE SINK EXCEEDS THE 2FT. |
| | |
| | 21) NOTE: THE GARAGE DOOR OPENER SHOWS A JUNCTION BOX |
| | FOR THE DOOR OPENER. IF THIS IS A HARDWIRED UNIT A |
| | DISCONNECT IS REQUIRED PER 422.30, 31. |
| | IF THIS IS GOING TO BE A PLUG IN TYPE UNIT USING THE |
| | EXCEPTION FOR SOME EQUIPMENT WHICH IS PERMITTED TO BE |
| | CORD AND PLUG CONNECTED AND USING THE PLUG AS THE |
| | DISCONNECTING MEANS PLEASE SHOW THE RECEPTACLE. |
| | |
| | 22) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING |
| | ALONG WALLS. ONE EXAMPLE WOULD BE THE WALL IN THE |
| | BREAKFAST AREA WHICH EXCEEDS 12FT BETWEEN COUNTER SPACE |
| | AND DOOR WAY OF GARAGE. AS ONLY ONE IS SHOWN THIS WOULD |
| | REQUIRE AN ADDITIONAL RECEPTACLE. |
| | PLEASE ALSO SEE MASTER BEDROOM FOR TWO FT WALL |
| | SPACE(S). |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |