| Date |
Text |
| 2009-01-16 11:44:40 | 2004 FBC W/2007 REVISIONS |
| | NEW TOWNHOUSE |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. (561) 233-5025 |
| | |
| | 3) THE STRUCTURE IS LOCATED IN AN "AO" FLOOD ZONE. AN |
| | ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | |
| | 4) R401.4 SOIL TESTS. |
| | IN AREAS LIKELY TO HAVE EXPANSIVE, COMPRESSIBLE, |
| | SHIFTING OR OTHER UNKNOWN SOIL CHARACTERISTICS, THE |
| | BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A |
| | SOIL TEST TO DETERMINE THE SOIL?S CHARACTERISTICS AT A |
| | PARTICULAR LOCATION. THIS TEST SHALL BE MADE BY AN |
| | APPROVED AGENCY USING AN APPROVED METHOD. SUBMIT A |
| | GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 5) FAC 61G-16.004(6) REQUIRES THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT TO APPEAR IN THE TITLE |
| | BLOCK ON EACH SHEET. |
| | |
| | 6) SUBMIT SIGNED AND SEALED TRUSS DRAWINGS THAT HAVE |
| | BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| | FOR THE STRUCTURE. R502.1.3.4 |
| | |
| | 7) SOME OF THE STRUCTURES IN THE PROJECT WILL BE |
| | LOCATED IN EXPOSURE CATEGORY C, WHICH REQUIRES HIGHER |
| | DESIGN PRESSURES THAN EXPOSURE B. IN ORDER FOR THE |
| | PLANS TO BE MASTERED, THE STRUCTURES WILL NEED TO BE |
| | DESIGNED EXPOSURE C, WHICH IS WORST CASE. SEE FBC |
| | R301.2.1.4 R301.2.1.4 EXPOSURE CATEGORY. |
| | FOR EACH WIND DIRECTION CONSIDERED, AN EXPOSURE |
| | CATEGORY THAT ADEQUATELY REFLECTS THE CHARACTERISTICS |
| | OF GROUND SURFACE IRREGULARITIES SHALL BE DETERMINED |
| | FOR THE SITE AT WHICH THE BUILDING OR STRUCTURE IS TO |
| | BE CONSTRUCTED. FOR A SITE LOCATED IN THE TRANSITION |
| | ZONE BETWEEN CATEGORIES, THE CATEGORY RESULTING IN THE |
| | LARGEST WIND FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN |
| | OF VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE |
| | FROM NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM |
| | CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE |
| | EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER |
| | STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF |
| | THE FOLLOWING CATEGORIES: 3. EXPOSURE C. OPEN TERRAIN |
| | WITH SCATTERED OBSTRUCTIONS, INCLUDING SURFACE |
| | UNDULATIONS OR OTHER IRREGULARITIES, HAVING HEIGHTS |
| | GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING MORE |
| | THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE IN ANY |
| | QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY |
| | BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE |
| | THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF |
| | EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE |
| | OF MORE THAN 600 FEET (182.9 M). SHORT-TERM (LESS THAN |
| | TWO YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE, |
| | FOR THE PURPOSES OF DEVELOPMENT, SHALL NOT BE |
| | CONSIDERED OPEN FIELDS. WHERE DEVELOPMENT BUILD OUT |
| | WILL OCCUR WITHIN THREE YEARS AND THE RESULTANT |
| | CONDITION WILL MEET THE DEFINITION OF EXPOSURE B, |
| | EXPOSURE B SHALL BE REGULATING FOR THE PURPOSE OF |
| | PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, |
| | GRASSLANDS AND OCEAN OR GULF SHORELINES. THIS CATEGORY |
| | DOES NOT INCLUDE INLAND BODIES OF WATER THAT PRESENT A |
| | FETCH OF 1 MILE (1.61 KM) OR MORE OR INLAND WATERWAYS |
| | OR RIVERS WITH A WIDTH OF 1 MILE (1.61 KM) OR MORE (SEE |
| | EXPOSURE D). |
| | |
| | 8) SHOW COMPLIANCE WITH R314.4 THERMAL BARRIER. |
| | UNLESS OTHERWISE NOTED IN SECTION R314.5, FOAM PLASTIC |
| | SHALL BE SEPARATED FROM THE INTERIOR OF A BUILDING BY |
| | AN APPROVED THERMAL BARRIER OF MINIMUM 0.5 INCH (12.7 |
| | MM) GYPSUM WALLBOARD OR AN APPROVED FINISH MATERIAL |
| | EQUIVALENT TO A THERMAL BARRIER MATERIAL THAT WILL |
| | LIMIT THE AVERAGE TEMPERATURE RISE OF THE UNEXPOSED |
| | SURFACE TO NO MORE THAN 250?F (121?C) AFTER 15 MINUTES |
| | OF FIRE EXPOSURE COMPLYING WITH THE ASTM E 119 STANDARD |
| | TIME TEMPERATURE CURVE. THE THERMAL BARRIER SHALL BE |
| | INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE |
| | FOR 15 MINUTES BASED ON NFPA 286 WITH THE ACCEPTANCE |
| | CRITERIA OF SECTION R315.4, FM4880, UL 1040, OR UL |
| | 1715. |
| | |
| | 9) SHOW COMPLIANCE WITH R314.5.3 ATTICS. |
| | WHERE ATTIC ACCESS IS REQUIRED BY SECTION R807.1 AND |
| | WHERE ENTRY IS MADE ONLY FOR SERVICE OF UTILITIES, FOAM |
| | PLASTICS SHALL BE PROTECTED AGAINST IGNITION BY |
| | 1.5-INCH-THICK (38 MM) MINERAL FIBER INSULATION, |
| | 1/4-INCH-THICK (6.4 MM) WOOD STRUCTURAL PANELS, |
| | 3/8-INCH (9.5 MM) PARTICLEBOARD, 1/4-INCH (6.4 MM) |
| | HARDBOARD, 3/8-INCH (9.5 MM) GYPSUM BOARD, OR |
| | CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS |
| | OF 0.016 INCH (0.406 MM) AND THE THERMAL BARRIER |
| | SPECIFIED IN SECTION R314.4 IS NOT REQUIRED. THE |
| | IGNITION BARRIER IS NOT REQUIRED WHERE THE FOAM PLASTIC |
| | INSULATION HAS BEEN TESTED IN ACCORDANCE WITH SECTION |
| | R314.6. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND EVALUATION |
| | REPORT FOR THE SPRAY FOAM INSULATION. SEE COMMENTS 8 |
| | AND 9 ABOVE. |
| | |
| | 11) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING |
| | FASTENINGS. |
| | WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO |
| | ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON |
| | CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE |
| | FRAMING. WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, |
| | 0.42 < G < 0.49 IS USED, SPACING OF RING-SHANK |
| | FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 |
| | FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE |
| | WITH FIGURE R803.2.3.1. |
| | |
| | 12) THE TWO HOUR FIRE WALL AND 4 FEET OF 5/8" TYPE X |
| | GYPSUM BOARD WITH CLASS C ROOF COVERING IS REQUIRED AT |
| | THE REAR PATIOS. R317.2.1 CONTINUITY. |
| | THE COMMON WALL FOR TOWNHOUSES SHALL BE CONTINUOUS FROM |
| | THE FOUNDATION TO THE UNDERSIDE OF THE ROOF SHEATHING, |
| | DECK OR SLAB AND SHALL EXTEND THE FULL LENGTH OF THE |
| | COMMON WALL INCLUDING WALLS EXTENDING THROUGH AND |
| | SEPARATING ATTACHED ACCESSORY STRUCTURES. ALSO SEE |
| | 317.2 AND R317.2.2. |
| | |
| | 13) THE TRUSS LEDGER NOTES ON THE DETAIL FOR TRUSSES |
| | PERPENDICULAR TO THE WALL ON SHEET S-2 AND THE NOTES ON |
| | THE FLOOR FRAMING PLAN ON S-2 DO NOT CORRESPOND. PLEASE |
| | COORDINATE THE NOTES. R301.1 |
| | |
| | 14) ON SHEET A-3.0 THE WIND PRESSURES FOR SOME OPENINGS |
| | DO NOT MATCH THE PRESSURES IN THE WINDOW AND DOOR |
| | SCHEDULE ON THE TYPICAL UNIT DRAWINGS. PLEASE |
| | COORDINATE. SEE GARAGE DOORS AND WINDOWS B & C. |
| | R301.2.1 |
| | |
| | 15) ON SHEET A3.0 THE WINDOWS IN THE GARAGES THAT FACE |
| | TOWARD THE ENTRANCES ARE NOT MARKED FOR WIND PRESSURES. |
| | R301.2.1 |
| | |
| | 16) ON SHEET A-5 THERE APPEARS TO BE SOME CONFUSION |
| | REGARDING HANDRAILS AND GUARDS. A HANDRAIL DETAIL IS |
| | SHOWN WITH A HEIGHT OF 42". PLEASE REVISE. R311.5.6 |
| | HANDRAILS.HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE |
| | SIDE OF EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH |
| | FOUR OR MORE RISERS.R311.5.6.1 HEIGHT. HANDRAIL HEIGHT, |
| | MEASURED VERTICALLY FROM THE SLOPED PLANE ADJOINING THE |
| | TREAD NOSING, OR FINISH SURFACE OF RAMP SLOPE, SHALL BE |
| | NOT LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38 |
| | INCHES (965 MM). EXCEPTION: WHEN FITTINGS ARE USED TO |
| | PROVIDE TRANSITION BETWEEN FLIGHTS, TRANSITION FROM |
| | HANDRAIL TO GUARDRAIL, OR USED AT THE START OF A STAIR, |
| | THE HANDRAIL HEIGHT AT THE FITTING SHALL BE PERMITTED |
| | TO EXCEED THE MAXIMUM HEIGHT. R312.1 GUARDS REQUIRED. |
| | PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED |
| | MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR GRADE |
| | BELOW SHALL HAVE GUARDS NOT LESS THAN 36 INCHES (914 |
| | MM) IN HEIGHT. OPEN SIDES OF STAIRS WITH A TOTAL RISE |
| | OF MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR |
| | GRADE BELOW SHALL HAVE GUARDS NOT LESS THAN 34 INCHES |
| | (864 MM) IN HEIGHT MEASURED VERTICALLY FROM THE NOSING |
| | OF THE TREADS. |
| | |
| | 17) ON SHEET A-5 PLEASE CLARIFY THAT THE WINDOW AND |
| | DOOR ASSEMBLIES ARE REQUIRED TO BE ANCHORED THROUGH THE |
| | 1 X BUCKS INTO THE CONCRETE OR OTHER SUBSTRATE. |
| | R613.6.1.1 MASONRY, CONCRETE OR OTHER STRUCTURAL |
| | SUBSTRATE. WHERE THE WOOD SHIM OR BUCK THICKNESS IS |
| | LESS THAN 1-1/2 INCHES (38 MM), WINDOW AND DOOR |
| | ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN FRAME OR |
| | BY JAMB CLIP OR SUBFRAME SYSTEM, IN ACCORDANCE WITH THE |
| | MANUFACTURERS PUBLISHED INSTALLATION INSTRUCTIONS. |
| | ANCHORS SHALL BE SECURELY FASTENED DIRECTLY INTO THE |
| | MASONRY, CONCRETE OR OTHER STRUCTURAL SUBSTRATE |
| | MATERIAL. UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND |
| | BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME |
| | SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS |
| | SHALL BE MADE FROM MATERIALS CAPABLE OF SUSTAINING |
| | APPLICABLE LOADS, LOCATED AND APPLIED IN A THICKNESS |
| | CAPABLE OF SUSTAINING APPLICABLE LOADS. ANCHORS SHALL |
| | BE PROVIDED TO TRANSFER LOAD FROM THE WINDOW OR DOOR |
| | FRAME TO THE ROUGH OPENING SUBSTRATE. |
| | |
| | 18) THE 2 HOUR FIRE RATED ADJACENT SEPARATION WALLS ARE |
| | REQUIRED TO BE INSULATED FROM THE BLOCK TO THE SPRAY |
| | FOAM INSULATION AT THE ROOF. PLEASE SPECIFY INSULATION |
| | TYPE AND R-VALUE ON THE PLANS AT THE WOOD TRUSS SECTION |
| | OF THE 2 HOUR FIRE RATED ASSEMBLY. ALSO REVISE ENERGY |
| | CALCULATION FORMS TO INCLUDE THIS AREA. FBC 13-6. |
| | |
| | 19) THE INSULATION FOR THE RAISED WOOD FLOOR ABOVE THE |
| | GARAGE AND PATIO ARE SPECIFIED AS R-13 ON THE PLANS AND |
| | R-19 ON THE ENERGY CALCULATIONS. PLEASE REVISE. FBC |
| | 13-6. |
| | |
| | 20) PLEASE SPECIFY THE INSULATION FOR THE RAISED WOOD |
| | FLOOR ABOVE THE FRONT ENTRY ON THE FLOOR PLANS. FBC |
| | 13-6. |
| | |
| | 21) THE INSULATION FOR THE WOOD FRAME WALL BETWEEN THE |
| | GARAGE AND THE CONDITIONED SPACE IS SPECIFIED AS R-11 |
| | ON THE FLOOR PLANS AND R-19 ON THE ENERGY CALCULATION |
| | FORMS. PLEASE CORRECT. FBC 13-6 |
| | |
| | 22) THE EXTERIOR AND ADJACENT BLOCK WALLS ARE SPECIFIED |
| | WITH R4.1 ON THE ENERGY CALCS. AND THE ADJACENT BLOCK |
| | INSULATION IS SPECIFIED AS R-3.0 ON THE PLANS. PLEASE |
| | REVISE. FBC 13-6. |
| | |
| | 23) PLEASE SUBMIT TWO COPIES OF THE PRODUCT APPROVALS |
| | FOR THE SKYTUBE SKYLIGHT SHOWN ON THE PLANS. DCA/FAC |
| | RULE 9B-72 |
| | |
| | 24) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 25) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | CONCRETE ROOF TILE IS INCOMPLETE. SUBMIT TWO COPIES OF |
| | AN NOA OR OTHER APPROVED EVALUATION REPORT INCLUDING |
| | INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE |
| | 9B-72. SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE |
| | USED TO INSTALL THE TILE. R905.3 |
| | |
| | 26) THE PRODUCT APPROVALS FOR THE WINDOW MULLIONS |
| | SPECIFY A DESIGN PRESSURE OF 48 PSF BASED ON THE CHARTS |
| | IN THE NOA FOR THE OPENING SIZE AND MULLION LENGTH. |
| | THIS MAY NOT BE ADEQUATE IF THE EXPOSURE CATEGORY IS |
| | CHANGED TO C WHICH WILL INCREASE THE DESIGN PRESSURES. |
| | PLEASE REVIEW. |
| | |
| | 27) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON |
| | THE PLANS. MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF |
| | EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE |
| | ROOF SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR |
| | ROOF ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18 |
| | RAD). R301.1 |
| | |
| | 28) R321.1 PREMISES IDENTIFICATION. APPROVED NUMBERS OR |
| | ADDRESSES SHALL BE PROVIDED FOR ALL NEW BUILDINGS IN |
| | SUCH A POSITION AS TO BE PLAINLY VISIBLE AND LEGIBLE |
| | FROM THE STREET OR ROAD FRONTING THE PROPERTY.THE |
| | BUILDINGS ARE REQUIRED TO HAVE APPROVED ADDRESSES |
| | BEFORE THE PERMITS WILL BE ISSUED. CONTACT JOHN NGUYEN |
| | AT 561-822-1239. |
| | |
| | 29) THE CANVAS AWNINGS SHOWN ON THE ELEVATIONS WILL |
| | REQUIRE SEPARATE PERMITS AND FEES. |
| | |
| | 30) THE ROOF FRAMING PLAN ON S-3 SHOWS A GIRDER TRUSS |
| | THAT IS ATTACHED TO THE TRUSS ASSEMBLY COMPRISING THE 2 |
| | HOUR FIRE RATED SEPARATION WALL. EXPLAIN HOW THIS |
| | DESIGN WILL NOT AFFECT THE FIRE RATING OF THE LISTED |
| | ASSEMBLY. PROVIDE DETAILS. R317.2 |
| | |
| | 31) THE NUMBER OF 10D X 1-1/2" NAILS FOR THE SIMPSON |
| | HETAL 20 AND HETA 16 CONNECTORS SHOULD BE (10) RATHER |
| | THAN THE (9) SPECIFIED IN THE TRUSS SCHEDULE ON S-3 FOR |
| | THE UPLIFT LOADS SPECIFIED. SEE 2008 SIMPSON CATALOG. |
| | |
| | 32) ON S-3 THE KEY FOR THE GYPSUM BOARD UNDER THE ROOF |
| | DECK HAS 1/2" TYPE X AND R 317.2.2 REQUIRES 5/8" TYPE |
| | X. PLEASE CORRECT. |
| | |
| | 33) THE ROOF DESIGN DOES NOT APPEAR TO PROVIDE PROPER |
| | SEPARATION AT THE GABLES AND HIP ROOFS THAT INTERSECT |
| | THE PROPERTY LINES. ADDITIONAL DETAILS AND TRUSS |
| | DRAWINGS ARE REQUIRED IN ORDER TO DETERMINE IF THE |
| | SEPARATION REQUIREMENTS OF R317.2 HAVE BEEN COMPLIED |
| | WITH. |
| | |
| | 34) THE GABLE ROOF OVERHANGS CAN NOT EXTEND BEYOND THE |
| | PROPERTY LINES. R302.1 EXTERIOR WALLS.EXTERIOR WALLS |
| | SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL HAVE NOT |
| | LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING WITH |
| | EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT EXTEND |
| | TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN |
| | ADJACENT PROJECTION OR WALL. |
| | |
| | 35) THE VALUE OF THE PRODUCT IS LOW AND HAS BEEN |
| | ADJUSTED. ADDITIONAL FEES OF $ 2877.30 ARE DUE. FBC |
| | 108.3* CITY AMENDMENTS. |
| | |
| | 36) IF THE PROJECT IS INTENDED TO BE "MASTERED" SUCH |
| | THAT ALL PERMIT DOCUMENTS DO NOT HAVE TO SUBMITTED WITH |
| | THE PERMIT APPLICATIONS FOR EACH INDIVIDUALLY PERMITTED |
| | TOWNHOUSE UNIT, PLEASE KNOW THAT ALL SUCH PERMITS MUST |
| | BE APPLIED FOR PRIOR TO THE IMPLEMENTATION OF THE 2007 |
| | FLORIDA BUILDING CODE ON MARCH 1, 2009. THE PROJECT |
| | WILL NEED TO BE "RE-MASTERED" TO COMPLY WITH THE 2007 |
| | FBC AT THAT TIME. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |