| Plan Review Notes For Permit 08120186 |
| Permit Number |
08120186 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-21 17:39:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SEE OPENING #9. A SPAN OF 8'7" HAS BEEN SPECIFIED | | | FOR A 104" OPENING SIZE. THE SPAN SHOULD EXCEED THE | | | OPENING HEIGHT BY AT LEAST 3" FOR A WALL MOUNT, 3" EDGE | | | DISTANCE. THE OPENINGS WHICH ARE 8'5"-8'8" IN HEIGHT | | | SHOULD USE THE COLUMN "SPAN UP TO 12'9" ON SHEET 8 | | | RATHER THAN THE COLUMN "SPANS UP TO 8'8" ". IT APPEARS | | | THAT SEVERAL OPENINGS ARE AFFECTED BY THE INCORRECT | | | SPANS. PLEASE REVISE SPANS AND ANCHOR SCHEDULE. | | | | | | WITH THE EXCEPTION OF THE SPANS (AND ANCHOR SPACING FOR | | | OPENINGS AFFECTED), ALL OTHER INFORMATION ON THE | | | INSTALLATION SCHEDULE APPEARS TO BE CORRECT/CODE | | | COMPLIANT. | | | |
|