2009-01-21 17:39:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE OPENING #9. A SPAN OF 8'7" HAS BEEN SPECIFIED
 FOR A 104" OPENING SIZE. THE SPAN SHOULD EXCEED THE
 OPENING HEIGHT BY AT LEAST 3" FOR A WALL MOUNT, 3" EDGE
 DISTANCE. THE OPENINGS WHICH ARE 8'5"-8'8" IN HEIGHT
 SHOULD USE THE COLUMN "SPAN UP TO 12'9" ON SHEET 8
 RATHER THAN THE COLUMN "SPANS UP TO 8'8" ". IT APPEARS
 THAT SEVERAL OPENINGS ARE AFFECTED BY THE INCORRECT
 SPANS. PLEASE REVISE SPANS AND ANCHOR SCHEDULE.
  
 WITH THE EXCEPTION OF THE SPANS (AND ANCHOR SPACING FOR
 OPENINGS AFFECTED), ALL OTHER INFORMATION ON THE
 INSTALLATION SCHEDULE APPEARS TO BE CORRECT/CODE
 COMPLIANT.
  