2008-12-17 12:29:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. INSTALLATION SCHEDULE STATES THAT DESIGN PRESSURES
 ARE +-120PSF, BUT ANCHOR SPACING FOR -62 HAS BEEN USED.
  
 2. SEE SHEET 7 REGARDING SHUTTER TO GLASS SEPARATION,
 AND REVISE INSTALLATION SCHEDULE.
  
 3. SPAN SHOULD CORRELATE WITH BLADE LENGTH. FOR
 INSTANCE, OPENING 1, 24" HEIGHT WITH A "7" FOR SPAN.
 PLEASE EXPLAIN HOW YOU'VE ARRIVED AT SPANS.
  
 4. OPENING 14, CONCRETE SUBSTRATE REQUIRES 3320PSI
 CONCRETE, SEE SHEET 8 OF THE PRODUCT APPROVAL. PLEASE
 PROVIDE INFORMATION REGARDING HOW YOU'VE DETERMINED
 THAT THE EXISTING CONCRETE FLOOR MEETS THIS
 REQUIREMENT.
  
 5. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS; IN THIS CASE, C1 THROUGH C5.
  
 6. TWO IDENTICAL SETS OF PERMIT DOCUMENTS REQUIRED.
 ONLY ONE INSTALLATION SCHEDULE AND FLOOR PLAN WERE
 PROVIDED.
  
 7. THE PRODUCT APPROVALS WERE SUBMITTED UNBOUND (LOOSE
 SHEETS). PLAN REVIEW WILL NOT FAIL FOR THIS REASON, BUT
 IT IS ADVISABLE TO SUBMIT DOCUMENTS BOUND IN TWO
 IDENTICAL COLLATED SETS. IF FOR SOME REASON THE SHEETS
 ARE OUT OF ORDER, AND TWO IDENTICAL SETS CANNOT BE
 EASILY PUT TOGETHER BY THE PLAN REVIEWER, THE
 CONTRACTOR WILL BE REQUIRED TO RESUBMIT WITH DOCUMENTS
 COLLATED.