| Plan Review Notes For Permit 08120178 |
| Permit Number |
08120178 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-16 15:36:37 | ***DENIED*** | | | | | | FIRE ALARM DRAWING APPEARS TO BE CODE COMPLIANT. PLEASE | | | SEE THE FOLLOWING COMMENTS: | | | | | | 1) EQUIPMENT SUBMITTALS FOR A SINGLE DOOR ACCESS SYSTEM | | | HAVE BEEN PROVIDED WITH THIS PERMIT APPLICATION. IF | | | ACCESS CONTROL EQUIPMENT IS INCLUDED IN THE SCOPE OF | | | THIS WORK, ILLUSTRATE SPECIFIC EQUIPMENT ON THE DRAWING | | | AND LEGEND. | | | | | | 2) ACCESS-CONTROLLED EGRESS DOORS SHAL COMPLY WITH THE | | | REQUIREMENTS OF NFPA 101, SEC. 7.2.1.6.2. | | | | | | 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|