| Plan Review Notes For Permit 08120128 |
| Permit Number |
08120128 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-02-19 11:21:32 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- CLARIFY WHICH SHUTTERS PRODUCT APPROVAL IS GOING TO | | | BE USED. FLORIDA PRODUCT APPROVAL FL 722 OR NOA | | | 06-0110.04. FLORIDA PRODUCT APPROVAL FL722 IS MISSING | | | THE DRAWINGS. | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | SELECTED PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 | | | CITY AMENDMENTS TO FBC 2004. | | | 3- A) PROVIDE COMPLETE INSTALLATION SCHEDULE FOR STORM | | | SHUTTERS. | | | B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS (EG: WALL MOUNTED, BUILT OUT, ETC) AND | | | ANCHOR TYPE AND SPACING TO BE USED. |
|