| 2008-12-16 16:52:33 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER1 |
| | FBC-2004 EXISTING BUILDING |
| | |
| | 1. PLEASE INDICATE WHICH UNIT WILL BE PERMITTED FOR |
| | WORK ON THE APPLICATION . PLANS SHOW APT A & APT B. |
| | SECTION 106.1.1. |
| | |
| | 2. SHT A1 SANITARY RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS. THE |
| | FIXTURE DOWNSTREAM OF THE W/C IS INDICATED AS A SINK ON |
| | THE RISER DIAGRAM, BUT A LAV ON THE FLOOR PLAN. THE |
| | FIXTURE IS NOT VENTED AS SHOWN, NOR IS THE TUB. IF THE |
| | SANITARY PIPING IS TO BE REPLACED, THEN IT SHALL BE |
| | CODE COMPLIANT. SECTIONS 106.1.1 & 909.1. (SEE RED LINE |
| | EXAMPLE ON ONE SET OF PLANS). INDICATE PIPE SIZES. |
| | |
| | 3. PLEASE SUBMIT A CODE SUMMARY SHOWING CODE IN EFFECT, |
| | (FBC-2004 W/20005, 2006 & 2007 AMENDMENTS), AND |
| | INDICATE THE LEVEL OF ALTERATION PER CHAPTER 3 OF THE |
| | EXISTING BUILD CODE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |