| 2008-12-30 10:02:06 | RESIDENTIAL (R3) REPAIRS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.0 OF FBC 2004. |
| | ***NOTE: MAKE SURE CORRECT 2004 REVISED FORM IS USED. |
| | ALSO, MAKE SURE ALL INFORMATION IS COMPLETED AND |
| | OWNER/AGENT SIGNS AND DATES BOTTOM OF FORM AS WELL. |
| | |
| | 2- CLEARLY IDENTIFY ON PLANS SCOPE OF WORK. CLEARLY |
| | IDENTIFY IF TENANT SEPARATION WALL IS GOING TO BE |
| | REPAIRED. IF SO, THEN PROVIDE SPECIFICATIONS FOR ONE |
| | HOUR FIRE RATED WALL AS REQUIRED BY SEC. R317.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 3- CLEARLY IDENTIFY WINDOWS TO BE REPLACED. SPECIFY |
| | TYPE OF EXISTING WINDOW (EG: SINGLE HUNG, HORIZONTAL |
| | SLIDER, ETC). TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310. |
| | |
| | 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR STORM |
| | SHUTTERS. SEE ATTACHED SAMPLE. ALSO, CLEARLY MARK ON |
| | SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS (EG: |
| | WALL MOUNTED, BUILD OUT, ETC) AND SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED. |
| | |
| | 5- PRODUCT APPROVAL SUBMITTED FOR ENTRY DOOR NEED TO BE |
| | REPLACED. ACCORDING TO MIAMI-DADE COUNTY WEBSITE NOA |
| | 07-0731.04 SUBMITTED IS CLOSED. SEE ATTACHED COPY FROM |
| | MIAMI-DADE COUNTY WEBSITE. NEED TO PROVIDE CURRENT AND |
| | ACTIVE PRODUCT APPROVAL. |
| | |
| | 6- ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE IN |
| | WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |