| 2008-12-10 10:07:51 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, NFPA-303 2000, 2004 |
| | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| | THE FOLLOWING: |
| | |
| | 1} PROVIDE MANUFACTURERS SPECIFICATIONS INCLUDING |
| | LISTING INFORMATION, FOR THE FIXTURES AND FIRE |
| | EXTINGUISHER STORAGE EQUIPMENT THAT ARE INTENDED TO BE |
| | INSTALLED UNDER THIS PERMIT. |
| | |
| | 2} INDICATE THE TYPE OF JUNCTION BOXES SHOWN ON THE |
| | "TYPICAL LIGHT POLE INSTALLATION" CUT, SHEET EP3-02, |
| | AND A CLEARER CUT OF THE INSTALLATION METHOD. MUST |
| | COMPLY WITH 3.10.5.2, NFPA-303 (2000 ED).. |
| | |
| | 3} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER |
| | 106.1.1 FBC AS AMENDED. |
| | |
| | 4} SEE NFPA STANDARDS ON SHEET G-2. THE REFERENCE TO |
| | NFPA-303, SHOULD REFERENCE THE 2000 EDITION INSTEAD OF |
| | 2006, THAT IS THE REFERENCE IN ARTICLE 555 OF THE 2005 |
| | NEC, CURRENTLY ADOPTED. |
| | |
| | 5} THE "FLEX CABLE" SHOWN ON CUT #2, SHEET EP3-02 MUST |
| | COMPLY WITH 555.13(A)(2) NEC, 3.10.5 NFPA-303, WITH A |
| | UL LISTING OF PDYQ OR QPMU OR COMPARABLE. INDICATE THE |
| | TYPE INTENDED FOR USE ON THE PLAN. |
| | |
| | 6} REGARDING THE "STAINLESS STEEL SUPPORT BRACKET", |
| | SAME SHEET AND CUT IN COMMENT #5, SEE |
| | 555-13(B)(4)(A)(3) "CABLES SHALL BE SECURELY FASTENED |
| | BY NONMETALLIC CLIPS TO STRUCTURAL MEMBERS OTHER THAN |
| | THE DECK PLANKING.". |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |