| Notes |
| Date |
Text |
| 2008-12-18 09:11:23 | BUILDING PLAN REVIEW | | | PERMIT: 08120123 | | | ADD: 100 S. FLAGLER DR. | | | CONT: WHITING TURNER CONTRACTING | | | TEL: (954)776-0800 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 12-18-08 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) SHEET RP3-1: THE ACCESSIBLE RAMP DETAIL #2 FAIL TO | | | SHOW THE HANDRAILS. 11.4.8.5. HANDRAILS: IF A RAMP HAS | | | A RISE GREATER THAN 6" OR A HORIZONTAL PROJECTION | | | GREATER THAN 72", THEN IT SHALL HAVE HANDRAILS ON BOTH | | | SIDES. 11-4.8.7: RAMPS AND LANDINGS WITH DROP-OFFS | | | SHALL HAVE CURBS, WALLS, RAILINGS, OR PROJECTING | | | SURFACES THAT PREVENT PEOPLE FROM SLOPPING OFF THE | | | RAMP. CURBS SHALL BE A MINIMUM OF 2 INCHES HIGH (SEE | | | FIGURE 17). THE HANDRAIL EXTENSION SHALL COMPLY WITH | | | SECTION 11-4.4 WHERE THE BOTTOM OF THE EXTENSION SHALL | | | BE A MAXIMUM OF 27 INCHES SEE FIGURE 8(C) AND 8(D). | | | | | | 2) THE PLANS NEED TO CLEARLY INDICATE THE LENGTH AND | | | WIDTH OF THE DOCK AND GANGWAY. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | PHONE (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | |
|