2008-12-08 11:16:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. PROVIDE INFORMATION REGARDING THE TRAVERTINE
 THICKNESS AND APPROXIMATE WEIGHT PSF, FBC16.
  
 2. AN ENGINEERING ANALYSIS IS REQUIRED TO DEMONSTRATE
 THAT THE EXISTING SLAB CAN ACCOMODATE THE ADDITIONAL
 ANTICIPATED DEAD LOAD, FBC16. TWO CITY PLAZA MANAGEMENT
 IS WORKING TO GET AN ENGINEER'S LETTER ON FILE.
 HOWEVER, THIS HAS NOT BEEN DONE AT THIS TIME. PLEASE
 PROVIDE ENGINEERING. IF THIS IS NOT POSSIBLE, THIS
 PERMIT CAN BE ISSUED WITH PROVISO THAT THE LETTER WILL
 BE SUBMITTED PRIOR TO FINAL INSPECTION.
  