Plan Review Notes
Plan Review Notes For Permit 08120105
Permit Number 08120105
Review Stop G
Sequence Number 2
Notes
Date Text
2008-12-15 09:36:00DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE CUT SECTIONS FROM THE METER TO THE
 FIRST TEE SERVING THE APPLIANCES IN THE HOUSE AND THE
 SECTION FROM THE TEE TO THE DROP FOR THE GENERATOR ARE
 NOT INDICATED ON THE PLANS. ALSO THE RISERS FROM THE PE
 PIPE TO THE GENERATOR AND TO THE GRILL ARE INDICATED AS
 1 FOOT. PER SECTION 404.9 THE MINIMUM BURIAL DEPTH
 REQUIRED IS 12 INCHES. THAT WOULD MAKE THE GRILL SHUT
 OFF VALVE AND THE GENERATOR SHUT OFF VALVE AT GROUND
 LEVEL. PLEASE CLARIFY AND SHOW ALL CUT SECTION LENGTHS
 AS THEY WILL BE INSTALLED.
 ****NEW RISER DIAGRAM SUBMITTED. THE NEW RISER DIAGRAM
 STILL DOES NOT SHOW THE LENGTH OF PIPE FROM THE SECOND
 TEE FROM THE METER TO THE DROP TO THE HOUSE. IS THE
 FIRST TEE ON THE METER AS SHOWN? ALSO THE COMMENT
 CONCERNING THE RISERS FROM THE PE PIPE TO THE
 GENERATOR, GRILL AND NOW THE POOL HEATER HAS NOT BEEN
 ADDRESSED. PLEASE CLARIFY.
  
 2. OK
 3. OK
 4. OK
  
 5. PER SECTION 409.4 A SHUT OFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF THE REGULATORS. ALSO A
 UNION IS REQUIRED BY ALL REGULATORS THAT ARE NOT AT THE
 APPLIANCE SUCH AS THE HOUSE REGULATOR. PLEASE INDICATE
 ON RISER DIAGRAM.
 ****SHUT OFF VALVES ARE SHOWN DOWNSTREAM OF THE
 REGULATORS. THE SHUT OFF VALVE SHALL BE INSTALLED
 UPSTREAM OF THE REGULATORS.
  
 **********NEW COMMENTS**********
  
 1B. REGULATORS INDICATED FOR THE TANKLESS WATER HEATER,
 POOL HEATER & GENERATOR, MAXITROL 325-3 ARE ONLY
 INDICATED FOR MAXIMUM INDIVUAL LOAD AT 140,000 BTU. THE
 GAS FIXTURES EXCEED THE MAXIMUM. PLEASE INDICATE
 REGULATORS THAT COMPLY SUCH AS THE MAXITROL 325-5AL.
  
 2B. THE TOTAL DEVELOPED LENGTH IS INDICATED AS 35 FEET,
 BUT THIS DOES NOT CORRELATE WITH THE CUT LENGTHS
 INDICATED ON THE RISER DIAGRAM AND COMMENT #1 WHEN
 CLARIFIED. PLEASE INDICATED THE DISTANCE FROM THE METER
 TO THE MOST REMOTE OUTLET. FUEL GAS APPENDIX A-USE OF
 CAPACITY TABLES A.3.1(4).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  