| Date |
Text |
| 2008-12-09 10:16:21 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE CUT SECTIONS FROM THE METER TO THE |
| | FIRST TEE SERVING THE APPLIANCES IN THE HOUSE AND THE |
| | SECTION FROM THE TEE TO THE DROP FOR THE GENERATOR ARE |
| | NOT INDICATED ON THE PLANS. ALSO THE RISERS FROM THE PE |
| | PIPE TO THE GENERATOR AND TO THE GRILL ARE INDICATED AS |
| | 1 FOOT. PER SECTION 404.9 THE MINIMUM BURIAL DEPTH |
| | REQUIRED IS 12 INCHES. THAT WOULD MAKE THE GRILL SHUT |
| | OFF VALVE AND THE GENERATOR SHUT OFF VALVE AT GROUND |
| | LEVEL. PLEASE CLARIFY AND SHOW ALL CUT SECTION LENGTHS |
| | AS THEY WILL BE INSTALLED. |
| | |
| | 2. TYPE OF GAS, (LP OR NATURAL). - INDICATE ON PLANS. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - THE TOTAL BTU LOAD DOES NOT ADD UP TO THE |
| | TOTAL INDICATED ON THE PLANS. PLEASE CORRELATE AND |
| | INDICATE THE CORRECT TOTAL. |
| | |
| | 4. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - DELIVERY |
| | PRESSURE IS INDICATED AT 2-PSI, BUT NO REGULATOR IS |
| | INDICATED FOR THE TANKLESS WATER HEATER. |
| | |
| | 5. PER SECTION 409.4 A SHUT OFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF THE REGULATORS. ALSO A |
| | UNION IS REQUIRED BY ALL REGULATORS THAT ARE NOT AT THE |
| | APPLIANCE SUCH AS THE HOUSE REGULATOR. PLEASE INDICATE |
| | ON RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |