Plan Review Notes
Plan Review Notes For Permit 08120105
Permit Number 08120105
Review Stop G
Sequence Number 1
Notes
Date Text
2008-12-09 10:16:21DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE CUT SECTIONS FROM THE METER TO THE
 FIRST TEE SERVING THE APPLIANCES IN THE HOUSE AND THE
 SECTION FROM THE TEE TO THE DROP FOR THE GENERATOR ARE
 NOT INDICATED ON THE PLANS. ALSO THE RISERS FROM THE PE
 PIPE TO THE GENERATOR AND TO THE GRILL ARE INDICATED AS
 1 FOOT. PER SECTION 404.9 THE MINIMUM BURIAL DEPTH
 REQUIRED IS 12 INCHES. THAT WOULD MAKE THE GRILL SHUT
 OFF VALVE AND THE GENERATOR SHUT OFF VALVE AT GROUND
 LEVEL. PLEASE CLARIFY AND SHOW ALL CUT SECTION LENGTHS
 AS THEY WILL BE INSTALLED.
  
 2. TYPE OF GAS, (LP OR NATURAL). - INDICATE ON PLANS.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - THE TOTAL BTU LOAD DOES NOT ADD UP TO THE
 TOTAL INDICATED ON THE PLANS. PLEASE CORRELATE AND
 INDICATE THE CORRECT TOTAL.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - DELIVERY
 PRESSURE IS INDICATED AT 2-PSI, BUT NO REGULATOR IS
 INDICATED FOR THE TANKLESS WATER HEATER.
  
 5. PER SECTION 409.4 A SHUT OFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF THE REGULATORS. ALSO A
 UNION IS REQUIRED BY ALL REGULATORS THAT ARE NOT AT THE
 APPLIANCE SUCH AS THE HOUSE REGULATOR. PLEASE INDICATE
 ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved