| Plan Review Notes For Permit 08120102 |
| Permit Number |
08120102 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-13 15:00:39 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | | | | 1. SHT PE.1 NEW SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. THE TUB, SHOWER, AND WASH MACHINE | | | SHALL BE TRAPPED. SECTION 1002.1. THE WASH MACHINE | | | REQUIRES A STANDPIPE PER SECTION 1002.1 & SHALL CONFORM | | | TO SECTION 802.4. THE RISER INDICATES TRAPS FOR THE LAV | | | UNDERGROUND. THE TRAPS SHALL BE PLACED AS CLOSE AS | | | POSSIBLE TO THE FIXTURE OUTLET AND THE VERTICLE | | | DISTANCE FROM THE FIXTURE OUTLET TO THE TRAP WEIR SHALL | | | NOT EXCEED 24 INCHES. SECTION 1002.1. PLEASE SEE RED | | | LINE INFORMATION ON ONE SET OF PLANS AND CORRECT PLANS | | | SO THEY MEET THESE CODE REQUIREMENTS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|