| Plan Review Notes For Permit 08120094 |
| Permit Number |
08120094 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-04-22 10:11:37 | REVISION, BUILDING REVIEW APPROVED WITH PROVISO. | | | | | | 1- MASTER BATHROOM WINDOW WAS REVISED TO BE NON-IMPACT | | | WINDOW. THIS WINDOW NEEDS TO HAVE SAFETY GLAZING AS | | | REQUIRED BY SEC. R308.4(5) OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR STORM SHUTTERS. AND, CLEARLY MARK ON | | | SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS (EG: | | | WALL MOUNTED, BUILT OUT, ETC) AND SPECIFIC ANCHOR TYPE | | | AND SPACING TO BE USED. | | | | | | 3- PROVIDE ALL INFORMATION REQUESTED ON PROVISO DATED | | | 1-12-09 TO AVOID ANY CONFLICTS OR DELAYS. SEE ATTACHED | | | COPY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|