| Plan Review Notes For Permit 08120094 |
| Permit Number |
08120094 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-12 14:45:11 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- RE-SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR: | | | A) SINGLE HUNG WINDOWS: *NEED TO PROVIDE CODE VERSION | | | 2004, NOT 2007. **MAKE SURE PRODUCT APPROVAL MEETS THE | | | CALCULATED DESIGN PRESSURES. ***ARCHITECT'S PLANS CALL | | | FOR IMPACT WINDOWS. PRODUCT APPROVAL SUBMITTED IS FOR | | | NON-IMPACT WINDOWS. | | | | | | B) WINDOW MULLIONS. AND, CLEARLY SPECIFY ON DRAWINGS | | | MULLION SIZE AND FASTENING METHOD. | | | | | | C) ALL SIMPSON STRUCTURAL CONNECTORS. NEED TO PROVIDE | | | 2004 CODE VERSION, NOT 2007. | | | | | | D) SHUTTERS: NEED TO PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. AND, MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS (EG: WALL MOUNT, BUILD OUT, ETC.) AND | | | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED. | | | ***NOTE: ARCHITECTURAL PLANS CALL FOR IMPACT WINDOWS. | | | THEREFORE, THIS MAY NOT BE REQUIRED. | | | | | | 2- ARCHITECT TO REVIEW AND APPROVED IN WRITING ALL | | | PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 3- EXTERIOR STAIRS NEED TO COMPLY WITH THE RISER/TREAD | | | RATIO OF SEC. R311.5.3.2. |
|