2008-12-04 16:41:28DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A1 DEMO/PROPOSED NOTES NUMBER INDICATES REMOVAL
 OF KITCHEN CABINETS AND FIXTURES IN ITS ENTIRITY, BUT
 DOES NOT SHOW THEM REINSTALLED. ALSO THE LAUNDRY DOES
 NOT SHOW A WASH MACHINE CONNECTION AS REQUIRED IN TABLE
 403.1. PLEASE CLAIFY. -- SUBMIT AN EXISTING FLOOR PLAN
 SO THAT THE EXTENT OF THE WORK CAN BE VERIFIED. SECTION
 106.1.2.
  
 2. SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL PIPE
 SIZES, P-TRAPS, AND VENTS. SHOW CONNECTIONS TO THE
 STACKS AND INDICATE EXISTING FIXTURES BELOW OR ON THE
 SAME FLOOR CONNECTING TO THE EXISTING STACKS. SECTION
 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  