Plan Review Notes
Plan Review Notes For Permit 08120094
Permit Number 08120094
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-09 11:53:46RESIDENTIAL (R3) REMODEL/ALTERATION BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK UP.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) NEW SINGLE HUNG WINDOWS.
  
 B) WINDOW MULLIONS.
  
 C) FRENCH DOORS AS SHOWN ON PLANS.
  
 D) SHUTTERS IF WINDOWS/DOORS DON'T HAVE IMPACT GLAZING.
 NOTE: ALSO, PROVIDE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE
 USED AS REQUIRED BY CITY IMPLEMENTATION STANDARD FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION. SEE ATTACHED
 SAMPLE.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED TO
 SUBMIT COMPLETE REPORT. THIS APPLIES TO STRUCTURAL
 CONNECTORS ONLY.
  
 3- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- SPECIFY SAFETY GLASS FOR NEW WINDOWS IN MASTER BATH
 AS REQUIRED BY SEC. R308.4 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- ALL NEW EXTERIOR STAIRS NEED TO COMPLY WITH THE
 RISER TREAD RATIO OF SEC. R311.5.3.2 OF 2004 FLORIDA
 RESIDENTIAL CODE. REVISE PLANS AS REQUIRED.
  
 6- PROVIDE DIMENSIONS FOR NEW INTERIOR STAIRWAY TO
 VERIFY COMPLIANCE WITH SECTIONS R311.5.1 FOR STAIR
 WIDTH AND R311.5.4 FOR STAIR LANDING OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 7- PROVIDE DIMENSIONS FOR ROOM ADJACENT TO NEW STAIRS
 TO VERIFY COMPLIANCE WITH THE MINIMUM ROOM SIZES
 REQUIREMENTS OF SEC. R304 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 NOTE: WRITTEN DIMENSIONS (7'-6") SHOWN ON THE FLOOR
 PLANS DON'T MATCH SCALED DIMENSIONS. ARE THE FLOOR
 PLANS DRAWN TO SPECIFIED SCALE. ALSO, COORDINATE THIS
 ITEM WITH DIMENSIONS GIVEN ON ITEM #5 ABOVE. DRAW PLANS
 TO EXACT SCALE AND PROVIDE CORRESPONDING WRITTEN
 DIMENSIONS.
  
 8- SHEET A3: REVISE STRUCTURAL DESIGN CRITERIA AND
 CODES NOTE. WIND LOADS TO BE BASED ON ASCE 7-02 NOT
 ASCE 7-98. REVISE AS REQUIRED.
  
 9- SHEET A-5: REVISE TYPICAL RAILING DETAIL TO COMPLY
 WITH SEC. R311.5.6.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 NOTE: SEE ATTACHED TYPE II HANDRAIL DETAIL TAKEN FROM
 THE 2004 FLORIDA RESIDENTIAL CODE COMMENTARY FOR
 REQUIRED DIMENSIONS AND REVISE DETAIL AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  