Plan Review Notes
Plan Review Notes For Permit 08120078
Permit Number 08120078
Review Stop M
Sequence Number 1
Notes
Date Text
2008-12-14 12:32:10REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 200 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS AND RESUBMIT:
  
 1. THIS IS A PROPOSED ALTERATION TO AN EXISTING
 BUILDING. THE OWNER OR DESIGN PROFESSIONAL SHALL
 DECLARE A LEVEL OF ALTERATION AND DECLARE ON PLANS IN
 ACCORDANCE WITH FBCEB 301.5.
  
 2. MECHANICAL PLANS INDICATE "SUITEE" AND "EACH FLOOR."
 IS THIS WORK TO TAKE PLACE ON EACH FLOOR OF THE
 BUILDING? PLEASE INDICATE THE SPECIFIC ADDRESS LOCATION
 OF THE PROPOSED WORK ON THE PLANS IN ACCORDANCE WITH
 FBCB 106.1.1.
  
 3. MECHANICAL PLAN SHOWS WHAT APPEARS TO BE A
 RECTANGULAR DUCT IN THE HALL. IS THIS DUCT NEW,
 EXISTING, BEING MODIFIED? PLEASE CLARIFY THE SCOPE AND
 DIFFERENTIATE BETWEEN NEW AND EXISTING WORK IN
 ACCORDANCE WITH FBCB 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]