| Plan Review Notes For Permit 08120078 |
| Permit Number |
08120078 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-14 12:32:10 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: | | | FBC 2004 CODE FAMILY W/ 200 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS AND RESUBMIT: | | | | | | 1. THIS IS A PROPOSED ALTERATION TO AN EXISTING | | | BUILDING. THE OWNER OR DESIGN PROFESSIONAL SHALL | | | DECLARE A LEVEL OF ALTERATION AND DECLARE ON PLANS IN | | | ACCORDANCE WITH FBCEB 301.5. | | | | | | 2. MECHANICAL PLANS INDICATE "SUITEE" AND "EACH FLOOR." | | | IS THIS WORK TO TAKE PLACE ON EACH FLOOR OF THE | | | BUILDING? PLEASE INDICATE THE SPECIFIC ADDRESS LOCATION | | | OF THE PROPOSED WORK ON THE PLANS IN ACCORDANCE WITH | | | FBCB 106.1.1. | | | | | | 3. MECHANICAL PLAN SHOWS WHAT APPEARS TO BE A | | | RECTANGULAR DUCT IN THE HALL. IS THIS DUCT NEW, | | | EXISTING, BEING MODIFIED? PLEASE CLARIFY THE SCOPE AND | | | DIFFERENTIATE BETWEEN NEW AND EXISTING WORK IN | | | ACCORDANCE WITH FBCB 106.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|