Plan Review Notes
Plan Review Notes For Permit 08120078
Permit Number 08120078
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-12-11 13:13:57***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 106.1.1.
  
 3) ILLUSTRATE THE LOCATIONS OF REQUIRED SMOKE ALARMS.
 DEVICES SHALL BE LOCATED AT LEAST 3 FEET FROM AC
 DIFFUSERS.
  
 4) WILL WORK IMPACT EXISTING FIRE PROTECTION SYSTEMS?
  
 5) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, THE CONSTRUCTION OF SOFFITS SHALL NOT
 INTERFERE WITH REQUIRED SPRINKLER COVERAGE.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756