| Plan Review Notes For Permit 08120078 |
| Permit Number |
08120078 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-11 13:13:57 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. FBC 106.1.1. | | | | | | 3) ILLUSTRATE THE LOCATIONS OF REQUIRED SMOKE ALARMS. | | | DEVICES SHALL BE LOCATED AT LEAST 3 FEET FROM AC | | | DIFFUSERS. | | | | | | 4) WILL WORK IMPACT EXISTING FIRE PROTECTION SYSTEMS? | | | | | | 5) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM, THE CONSTRUCTION OF SOFFITS SHALL NOT | | | INTERFERE WITH REQUIRED SPRINKLER COVERAGE. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|