| 2008-12-11 11:52:53 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| | INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. |
| | |
| | 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED, ALL SHEETS. |
| | |
| | 3} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS. |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. NUMBER THE |
| | SHEETS FOR REFERENCE, USE SYMBOLS THAT ARE NATIONALLY |
| | RECOGNIZED IN PLACE OF ARROWS. PUT ALL PROPOSED |
| | ELECTRICAL WORK ON ONE SHEET. DIFFERENTIATE BETWEEN NEW |
| | AND EXISTING DEVICES WHERE NECESSARY SHOW CODE |
| | COMPLIANCE. |
| | |
| | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | 5} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER |
| | 106.1.1 FBC AS AMENDED.REMOVE THE NOTE INDICATING "EACH |
| | FLOOR", IF WORK IS TO BE DONE IN MORE THAN ONE UNIT, |
| | SEPARATE PERMITS ARE REQUIRED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |