| 2008-12-11 14:34:12 | SIGN, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION | | | IS TOO LOW. REVISE VALUATION TO INCLUDE INSTALLATION OF | | | SIGN ON THREE LOCATIONS AS SHOWN ON DRAWINGS AND ANY | | | DESIGN FEES AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS | | | TO FBC 2004. | | | ALSO, CLEARLY SPECIFY SIZE OF ALL LETTERS. | | | | | | 2- PROVIDE NOTICE OF COMMENCEMENT AS REQUIRED BY SEC. | | | 713.13 FLORIDA STATUTE. | | | | | | 2- PLEX LETTERS SPECS SHEET: | | | A) CLEARLY SPECIFY TYPE, SIZE AND NUMBER OF FASTENERS | | | TO BE USED PER LETTER AS REQUIRED TO VERIFY COMPLIANCE | | | WITH THE WIND LOADS OF SEC. 1609 FBC 2004. CLEARLY | | | IDENTIFY TYPE OF EXISTING WALL. "PIN MOUNTED TO WALL " | | | ARE NOT COMPLETE SPECIFICATIONS TO VERIFY COMPLIANCE | | | WITH THE WIND LOADS. | | | B) NEED TO PROVIDE THE NAME AND ORIGINAL SIGNATURE OF | | | PERSON WHO DESIGNED THE FASTENING METHOD AS REQUIRED BY | | | SEC. 106.1.3 OF CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|