| Plan Review Notes For Permit 08120054 |
| Permit Number |
08120054 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-11 15:10:30 | PLANS APPEAR TO BE CODE COMPLIANT. PLEASE SEE THE | | | FOLLOWING FOR CLARIFICATION: | | | | | | 1) DOOR SCHEDULE INDICATES (2) 1 HOUR RATED DOORS AND | | | DRAWINGS SHOW (2) 45 MINUTE DOORS. PLEASE CORRELATE | | | INFORMATION. | | | | | | 2) IF APPLICABLE, DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. SEE SHEET FA0.1 | | | | | | | | | PLANS WILL BE STAMPED WHEN RETURNED WITH THIS AND OTHER | | | REVIEW COMMENT CORRECTIONS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|