| 2009-01-16 09:41:54 | 2004 FBC W/2007 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR A | | | BUR ROOF SYSTEM NOA 06-0613.06 AND THE ENGINEERING THAT | | | WAS SUBMITTED REFERENCES NOA O7-0111.03 FOR A MODIFIED | | | ROOFING SYSTEM. PLEASE COORDINATE THE ENGINEERING WITH | | | THE PRODUCT APPROVAL. | | | | | | 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES AND | | | FASTENING OPTION LISTED IN THE NOA WILL BE USED. | | | | | | 3) THE FASTENER SPACING FOR ROOF ZONES 2 AND 3 | | | SPECIFIED IN THE ENGINEER'S SIGNED AND SEALED LETTER | | | HAS BEEN CHANGED BY SOMEONE. PLEASE SUBMIT 2 NEW SIGNED | | | AND SEALED RAS 117 CALCULATIONS WITHOUT HANDWRITTEN | | | CHANGES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|