| Plan Review Notes For Permit 08110567 |
| Permit Number |
08110567 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-26 14:28:12 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SEE PAGE 7 OF THE PRODUCT APPROVAL. BOTH "OPPOSING | | | CENTERMATES" AND "SYMMETRICAL CENTERMATES" WAS | | | HIGHLIGHTED. CLARIFY WHICH OPTION WILL BE USED, AS THIS | | | DETERMINES SHUTTER TO GLASS SEPARATION. | | | | | | 2. THE SHUTTER CONNECTION MOUNTING TYPE SHOULD | | | CORRELATE WITH THE ANCHOR CHARTS; FOR INSTANCE, WALL | | | MOUNT 1 (W/1" BO), SEE SHEET 10 OF THE PRODUCT | | | APPROVAL. | | | | | | 3. PLEASE EXPLAIN HOW YOU'VE ARRIVED AT THE SHUTTER | | | SPAN LENGTHS. IT APPEARS THAT A WALL MOUNT IS USED FOR | | | OPENING 1, SO THE SPAN SHOULD BE LARGER THAN THE | | | OPENING SIZE. | | | |
|