Plan Review Notes
Plan Review Notes For Permit 08110567
Permit Number 08110567
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-26 14:28:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PAGE 7 OF THE PRODUCT APPROVAL. BOTH "OPPOSING
 CENTERMATES" AND "SYMMETRICAL CENTERMATES" WAS
 HIGHLIGHTED. CLARIFY WHICH OPTION WILL BE USED, AS THIS
 DETERMINES SHUTTER TO GLASS SEPARATION.
  
 2. THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH THE ANCHOR CHARTS; FOR INSTANCE, WALL
 MOUNT 1 (W/1" BO), SEE SHEET 10 OF THE PRODUCT
 APPROVAL.
  
 3. PLEASE EXPLAIN HOW YOU'VE ARRIVED AT THE SHUTTER
 SPAN LENGTHS. IT APPEARS THAT A WALL MOUNT IS USED FOR
 OPENING 1, SO THE SPAN SHOULD BE LARGER THAN THE
 OPENING SIZE.
  