| 2009-01-28 15:36:02 | ******DENIED***** |
| | |
| | |
| | 1 THE ACTUAL/CORRECT ADDRESS SHALL BE IN THE TITLE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET. SEE SHEETS C1 THRU |
| | C5, EP1, AND LS-1 & LS-2. |
| | |
| | 2. ANY EXISTING AND/OR PROPOSED FIRE HYDRANT(S) SHALL |
| | BE IN SERVICE PRIOR, DURING, AND AFTER CONSTRUCTION. |
| | |
| | 3. ON SHEET A-104, ADD VERBAGE AS FOLLOWS: AS PER WEST |
| | PALM BEACH CODE, THE BUIDING'S ADDRESS NUMBERS SHALL BE |
| | NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH/STROKE; SUITE NUMBERS SHALL BE AT LEAST 3" HEIGHT |
| | AND AT LEAST 1" IN WIDTH/STROKE (SUITE NUMBERS OF AT |
| | LEAST 2"IN HEIGHT NEEDED ON REAR DOORS) . IT IS |
| | RECOMMENDED BY THIS WRITER THAT THE BUILDING ADDRESS |
| | NUMBERS BE AT LEAST 8" IN HEIGHT (REQUIREMENT OF PALM |
| | BEACH COUNTY) SINCE THIS SITE AREA OVERLAPS WITH PALM |
| | BEACH COUNTY. |
| | |
| | 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS |
| | AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | THIS MAY BE ADDED TO TO SHEET A-108 UNDER THE FINSH |
| | SCHEDULE. |
| | |
| | 5. FIRE DOORS (IF REQUIRED) SHALL COMPLY WITH NFPA 80. |
| | ADD COMMENT TO SHEET A-108 UNDER THE DOOR SCHEDULE. |
| | |
| | 6. INDICATE THE LOCATION OF THE 2A10:BC RATED FIRE |
| | EXTINGUISHERS WHICH SATIFIES THE 75'TRAVEL DISTANCE. |
| | |
| | 7. EXPLAIN WHY THERE IS NO EXIT/EMERGENCY LIGHTING IN |
| | THE VACAMT/FUTURE TENANT SPACE? |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMD |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |