| 2008-11-25 16:24:20 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. CLARIFY SCOPE OF WORK. THREE DIFFERENT PRODUCT |
| | APPROVALS WERE SUBMITTED. ON THE FLOOR PLAN, INDICATE |
| | WHICH WINDOW TYPE WILL BE INSTALLED AT EACH OPENING. |
| | FBC*106, FBC R301. |
| | |
| | 2. THE PRODUCT APPROVAL FOR JELDWEN, FL6338.10, IS |
| | INCOMPLETE. PLEASE PRINT THE FLORIDA STATE PRODUCT |
| | APPROVAL WITH THE INSTALLATION INSTRUCTIONS/EVALUATION |
| | REPORT FROM THE WEBSITE, WWW.FLORIDABUILDING.ORG. |
| | |
| | 3. THE PRODUCT APPROVAL FOR JELDWEN, FL9031.4, IS |
| | INCOMPLETE. PLEASE PRINT THE FLORIDA STATE PRODUCT |
| | APPROVAL WITH THE INSTALLATION INSTRUCTIONS/EVALUATION |
| | REPORT FROM THE WEBSITE, WWW.FLORIDABUILDING.ORG. |
| | |
| | 4. THE NOA SUBMITTED FOR THE PGT WINDOW IS FOR AN |
| | IMPACT RATED PRODUCT. WHERE WILL THIS BE INSTALLED? |
| | STORM PANEL PRODUCT APPROVALS WERE SUBMITTED; THEY ARE |
| | NOT REQUIRED FOR THIS WINDOW. FBC*106, FBC R301. |
| | |
| | 5. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS |
| | REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF. NUMBERING SHOULD CORRELATE WITH |
| | OPENING NUMBERS FOR WINDOWS ON THE FLOOR PLAN. |
| | |
| | 6. PROVIDE A REASONABLE VALUE FOR THIS JOB, LABOR AND |
| | MATERIALS. |
| | |
| | 7. THE APPLICATION STATES "IMPACT PROTECTION TO BE |
| | EFFECTED VIA STORM PANELS INSTALLED SEQUENTIALLY." WHAT |
| | DOES THIS MEAN? |
| | |
| | 8. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1. SEE ALSO COMMENT 1. |
| | |
| | |