| 2008-12-08 09:27:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. A PERMIT HAS ALREADY BEEN ISSUED FOR 08030015, SAME |
| | ADDRESS. PLEASE EXPLAIN WHY A SEPARATE PERMIT HAS BEEN |
| | APPLIED FOR. IF THERE ARE TWO PERMITS FOR THE SAME |
| | SCOPE OF WORK, A LETTER SHOULD BE SUBMITTED REQUESTING |
| | THAT ONE BE VOIDED. |
| | |
| | 2. THE LETTER SUBMITTED IS NOT SEALED. IN ORDER TO BE A |
| | PART OF THE PERMIT DOCUMENTS, THIS LETTER IS TO BE IN |
| | COMPLIANCE WITH FAC61G15-23, AND NEEDS TO INCLUDE AN |
| | IMPRESSED SEAL AS WELL AS THE CERTIFICATE OF |
| | AUTHORIZATION. THE LETTER IS REQUIRED OR HAVE THE |
| | INFORMATION INCORPORATED INTO THE SPECIFICATION. |
| | |
| | 3. THE DRAWING INDEX REFERS TO TWO DETAILS, SK-1 AND |
| | SK-2, BUT I WAS UNABLE TO LOCATE THESE PAGES IN THE |
| | DOCUMENTS SUBMITTED. |
| | |
| | 4. PROVIDE A TENDON LAYOUT PLAN SHOWING LOCATION OF |
| | REPAIR. THE SPECIFICATION STATES 4TH FLOOR. IS THIS |
| | LOCATED WITHIN A UNIT OR IN THE COMMON AREA? |
| | |
| | 5. THE ENGINEER STATES THAT AN "EXPEDITIOUS REPAIR" IS |
| | RECOMMENDED, BUT THE SPECIFICATION IS DATED FEBRUARY |
| | 15, 2008, ALMOST A YEAR AGO. IS THE STRUCTURAL |
| | INTEGRITY OF THE BUILDING AFFECTED? |
| | |
| | 6. THE SPECIFICATION IS TO BE IN COMPLIANCE WITH |
| | FAC61G15-23.002. THE INDEX SHEET DOES NOT CONTAIN A |
| | TITLE BLOCK WITH ALL REQUIRED INFORMATION. |
| | |
| | 7. PREINSPECT REQUIRED PER KEN CONRAD. THE PLANS HAVE |
| | BEEN ROUTED TO K. CONRAD. 561-805-6666 |
| | |
| | 8. AS THIS IS A THRESHOLD BUILDING, A THRESHOLD |
| | INSPECTOR MAY BE REQUIRED AFTER SCOPE/LOCATION OF WORK |
| | HAS BEEN DETERMINED. |
| | |
| | *****PLEASE CONTACT KEN CONRAD. 561-805-6666 FOR A |
| | PREINSPECT**** |
| | |