Plan Review Notes
Plan Review Notes For Permit 08110501
Permit Number 08110501
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-18 10:09:24** PROVISO**
  
 ** SPOKE TO DESIGNER OF RECORD. THE FOLLOWING ITEMS
 WILL NEED TO BE REVISED. THE DESIGNER OF RECORD STATED
 THAT PLANS WERE GOING TO HAVE SOME CHANGES ANYWAY AND
 WILL INCORPORATE THE REVISIONS AT THAT TIME.
  
  
 1) NOTE: THE PERFORMANCE CALCULATIONS SHOWN ON PLANS
 SHOW A LIGHTING LEVEL WATTAGE EXCEEDING THAT PERMITTED
 PER 13-415.2,13-415.2.B.2
 PLEASE SEE THE CONFERENCE ROOM WHICH IS OVER. THE
 ADDITIONAL ALLOWANCE FOR DECRETIVE LIGHTING IS
 PERMITTED HOWEVER FIXTURES MUST BE INSTALLED SPECIFIC
 TO THAT PURPOSE, UNDER SEPARATE CONTROL AND SHOWN ON
 THE CALCULATIONS UNDER ADDITIONAL ALLOWANCE.
 13-415.2.B.2
 THE NEW DESIGN TO BE SHOWN WILL NOT EXCEED ALLOWANCES.
  
 2) NOTE: THE PLANS CONTAIN NOTES FOR NEW CONTROLS
 MEETING CODE SECTIONS 13-415.1.ABC.1.1-.1.3 HOWEVER NEW
 OFFICE NEEDS TO SHOW NEW DEVICE.
 WENT OVER WITH DESIGNER AND HE WILL CHANGE PLANS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  