Plan Review Notes
Plan Review Notes For Permit 08110494
Permit Number 08110494
Review Stop G
Sequence Number 2
Notes
Date Text
2008-12-03 11:30:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SUBMIT THE FOLLOWING INFORMATION:
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (APPROX 29 FEET)
 ****RESPONSE NOTED, BUT DISTANCE IS INDICATED AT 19
 FEET AND CUT SECTIONS ADD UP TO 30 FEET. PLEASE
 CLAIRFY.
  
 5. OK (EXTERIOR)
 6. OK
 7. OK (INSPECTOR TO VERIFY COMPLIANCE)
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved