| Plan Review Notes For Permit 08110490 |
| Permit Number |
08110490 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-14 12:54:41 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS (OF 5) TAKEN FROM THE PREVIOUS | | | FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 3. PROVIDE AT LEAST ONE APPROVED PORTABLE FIRE | | | EXTINGUISHER HAVING A MINIMUM CAPACITY OF 18 LB DRY | | | CHEMICAL WITH B-C RATING. THE REQUIRED FIRE | | | EXTINGUISHER SHALL BE LOCATED NO MORE THAN 50 FEET FROM | | | THE STORAGE LOCATION. | | | | | | 4. THE CYCLINDER SHALL BE IN ACCORDANCE WITH DOT | | | SPECIFICATIONS AND SHALL BE MARKED AS PROVIDED IN THE | | | REGULATIONS, RULES, OR CODE UNDER WHICH IT IS | | | FABRICATED. | | | | | | 5. NFPA 704 LABELS, NO SMOKING, AND PRODUCT IDENTITY | | | LABELS WILL BE NEEDED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE THE ABOVE COMMENTS HAVE BEEN | | | ADDRESSED | | | | | | |
|