Plan Review Notes
Plan Review Notes For Permit 08110490
Permit Number 08110490
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-04-14 12:54:41*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF 5) TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 3. PROVIDE AT LEAST ONE APPROVED PORTABLE FIRE
 EXTINGUISHER HAVING A MINIMUM CAPACITY OF 18 LB DRY
 CHEMICAL WITH B-C RATING. THE REQUIRED FIRE
 EXTINGUISHER SHALL BE LOCATED NO MORE THAN 50 FEET FROM
 THE STORAGE LOCATION.
  
 4. THE CYCLINDER SHALL BE IN ACCORDANCE WITH DOT
 SPECIFICATIONS AND SHALL BE MARKED AS PROVIDED IN THE
 REGULATIONS, RULES, OR CODE UNDER WHICH IT IS
 FABRICATED.
  
 5. NFPA 704 LABELS, NO SMOKING, AND PRODUCT IDENTITY
 LABELS WILL BE NEEDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE ABOVE COMMENTS HAVE BEEN
 ADDRESSED
  
  