| Notes |
| Date |
Text |
| 2009-04-09 13:21:40 | ** DENIED** | | | | | | 1) NOTE: PLEASE KNOW THAT THE PERMIT IS APPLIED FOR | | | UNDER THE 2004 FBC W/ 2007 REVISIONS. THE PLANS STATE | | | DESIGNS ON ELECTRICAL AND ARCHITECTURAL SHEETS UNDER | | | 2007 FBC W/ 2009 REVISIONS. | | | PLEASE REVISE CODES. | | | WE DO NOT HAVE THE AUTHORITY TO RED-LINE PLANS FOR | | | CORRECT CODES. | | | | | | 2) NOTE: PLEASE SHOW A LAYOUT OF THE CLASS LOCATIONS | | | AND LIST. IS THE CLOUDED LOCATION THE CLASS LOCATION? | | | PLEASE LIST THE SPECIFIC TYPE OF LOCATION. | | | NEC 500 | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|