Plan Review Notes
Plan Review Notes For Permit 08110490
Permit Number 08110490
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-12-19 15:39:22*****UNSAT*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMEITTED PLAN SHEET. THIS WILL CLEARLY
 DISTINGUISH THAT THE PROJECTED SCOPE OF WORK IS DONE AT
 THE REFERENCED LOCATION AND NOT AT THE OTHER ADDRESSES
 SHOWN ON THE PLAN (1616 AND 1750 NORTH FLORIDA MANGO
 ROAD).
  
 2. THE STORAGE, USE, AND HANDLING OF LIQUIFIED
 PETROLEUM GASES SHALL COMPLY WITH NFPA 58.
  
 3. PROVIDE AT LEAST ONE APPROVED PORTABLE FIRE
 EXTINGUISHER HAVING A MINIMUM CAPACITY OF 18 LB DRY
 CHEMICAL WITH B-C RATING. THE REQUIRED FIRE
 EXTINGUISHER SHALL BE LOCATED NO MORE THAN 50 FEET FROM
 THE STORAGE LOCATION.
  
 4. THE CYCLINDER SHALL BE IN ACCORDANCE WITH DOT
 SPECIFICATIONS AND SHALL BE MARKED AS PROVIDED IN THE
 REGULATIONS, RULES, OR CODE UNDER WHICH IT IS
 FABRICATED.
  
 5. NFPA 704 LABELS, NO SMOKING, AND PRODUCT IDENTITY
 LABELS WILL BE NEEDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE ABOVE COMMENTS HAVE BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN FEVIEW
 561-805-6722