| 2008-12-19 15:39:22 | *****UNSAT***** | | | | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMEITTED PLAN SHEET. THIS WILL CLEARLY | | | DISTINGUISH THAT THE PROJECTED SCOPE OF WORK IS DONE AT | | | THE REFERENCED LOCATION AND NOT AT THE OTHER ADDRESSES | | | SHOWN ON THE PLAN (1616 AND 1750 NORTH FLORIDA MANGO | | | ROAD). | | | | | | 2. THE STORAGE, USE, AND HANDLING OF LIQUIFIED | | | PETROLEUM GASES SHALL COMPLY WITH NFPA 58. | | | | | | 3. PROVIDE AT LEAST ONE APPROVED PORTABLE FIRE | | | EXTINGUISHER HAVING A MINIMUM CAPACITY OF 18 LB DRY | | | CHEMICAL WITH B-C RATING. THE REQUIRED FIRE | | | EXTINGUISHER SHALL BE LOCATED NO MORE THAN 50 FEET FROM | | | THE STORAGE LOCATION. | | | | | | 4. THE CYCLINDER SHALL BE IN ACCORDANCE WITH DOT | | | SPECIFICATIONS AND SHALL BE MARKED AS PROVIDED IN THE | | | REGULATIONS, RULES, OR CODE UNDER WHICH IT IS | | | FABRICATED. | | | | | | 5. NFPA 704 LABELS, NO SMOKING, AND PRODUCT IDENTITY | | | LABELS WILL BE NEEDED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE THE ABOVE COMMENTS HAVE BEEN | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN FEVIEW | | | 561-805-6722 |
|