2008-12-04 16:37:38BUILDING PLAN REVIEW
 PERMIT: 08110490
 ADD: 1700 N. FLORIDA MANGO ROAD.
 CONT: SUPERIOR ENERGY SYSTEMS, LTD.
 TEL: (440)236-6009
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS NOT THE IBC. THIS
 INFORMATION IS ON THE DRAWINGS.
  
 4) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002, FLORIDA STATUTES 471 FOR ENGINEERS
 AND FL ADMIN CODE 61G16.003, FLORIDA STATUTES 481
 ARCHITECTS. THE SEALS AND SIGNATURES ON THE PLANS AND
 REPORTS SHALL BE ORIGINAL NOT PHOTO-COPIES. THE DESIGN
 PROFESSIONAL SHALL BE REGISTERED UNDER THE LAWS OF THE
 STATE OF FLORIDA.
  
 5) UNDER THE HEADING ON THE PERMIT APPLICATION
 ?DESCRIBE PROJECT IN DETAIL? STATES THE LPG FUEL TANK
 THAT WILL BE TEMPORARY (LESS THAN 180 DAYS). NOTE: IF
 THIS IS TEMPORARY STRUCTURE THE TIME LIMIT WILL BE 180
 DAYS. FBC 107.1 THE BUILDING OFFICIAL IS AUTHORIZED TO
 ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY
 USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF
 SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN 180
 DAYS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT
 EXTENSIONS FOR DEMONSTRATED CAUSES. PLEASE SEE FBC
 3103.1 FOR ADDITIONAL INFORMATION ON TEMPORARY
 STRUCTURES. IF THIS IS TRULY A TEMPORARY STRUCTURE,
 PROVIDE A NOTARIZE LETTER STATING THE DATE WHEN THE
 TANK WILL BE INSTALLED AND WHEN IT WILL BE REMOVED,
  
 6) PAGE #3 OF THE PROPANE TANK ANCHORAGE ANALYSIS
 INDICATES ASCE 7-05. THE ASCE REFERENCE STANDARD UNDER
 THE FBC 2004 IS ASCE 7-02 SEE CHAPTER 35 OF THE FBC
 PAGE 35.6R SHEET #2 OF THE PACKAGE ALSO MAKES REFERENCE
 TO THE 2006 IBC THIS INFORMATION IS ALSO INCORRECT. THE
 CODE USE HERE IN FLORIDA IS THE 2004 FBC WITH THE 2007
 REVISIONS. SHEET #4 SHOWS THE ?L? BRACKETS, BUT DO NOT
 CLEARLY STATE HOW THESE BRACKETS WILL BE ATTACHED TO
 THE TANK. ARE THESE BRACKETS WELDED TO THE TANK? THE
 DETAIL DOES NOT CLEARLY STATE HOW THE BRACKETS WILL
 HOLD THE TANK IN PLACE. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THE CODE. 106.1.1*
  
 7) FBC 1609.1.3STRUCTURAL MEMBERS AND SYSTEMS AND
 COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE A CONTINUOUS LOAD
 PATHS FOR THESE FORCES TO THE FOUNDATION.
  
 8) WHAT IS THE LENGTH, WIDTH AND THICKNESS OF THE
 CONCRETE SLAB? THE TYPE OF CONCRETE SHALL BE ALSO
 INDICATED, WILL IT BE 2500PSI, 3000PSI WITH 6X6 WIRE
 MESH OR WILL IT BE FIBER MESH CONCRETE? PROVIDE DETAIL
 DRAWINGS OF THE CONCRETE SLAB SHOWING THIS INFORMATION.
 PROVIDE MORE INFORMATION ON THE CRASH POSTS SHOWING HOW
 THEY ARE SECURED IN THE GROUND AND THE HEIGHT THEY ARE
 OFF THE GROUND AND THE DISTANCE FROM THE STORAGE TANK.
 WHEN ADDRESSING THE ZONING REVIEWER COMMENTS AND A
 FENCE IS CHOSEN PROVIDE INFORMATION HOW THE FENCE WILL
 MEET THE 140MPH WIND REQUIREMENTS. ADDITIONAL
 INFORMATION IS REQUIRED 106.1.2*
  